background image

modulating signal (observing 5 Vp limit) to set the car-
rier level.

3.2.6

FM Operation

2.0-

In FM operation, the instantaneous frequency of the

output signal varies with the instantaneous amplitude
of the modulating signal.

NOTE

1.4-

The output frequency modulation will not

b e   l i n e a r   w h e n   t h e   i n s t a n t a n e o u s
modulated frequency exceeds these range
limits.

Upper Limit: 2.0

x

FREQ MULT

Lower Limit:

0.001 x

 Upper Limit

Set up the generator as for continuous operation
(refer to paragraph 3.2.1). The frequency setting will
be the center frequency from which the modulated
signal will vary. Switch to internal or external FM
modulation. If internal, set the modulation generator
frequency as desired and sync on the modulation
generator signal. Set the modulation amplitude for the
amount of modulation desired. Because the main
generator is limited in frequency range (limited to ap-
proximately the dial range for any given multiplier set-
ting), the main generator frequency dial and the
modulation amplitude control. must be balanced to
stay within that range. The range is shown in figure 3-4

as the OUTPUT FREQUENCY FACTOR, which, when
multiplied by the FREQ MULT setting, gives the actual
output frequency. Example 1 shows the output being
swept over the full frequency range when the main
generator frequency dial is set at midpoint (1 .O), the

MOD AMPLITUDE control set at midrange and the
modulation signal is a balanced waveform (

,

or

); that is, the modulation generator voltage

swings both positive and negative. If the MOD
AMPLITUDE control is rotated toward ccw, the
voltage swing decreases and the angle subtended in
the nomograph decreases. If the MOD AMPLITUDE
control is rotated toward MAX, the angle subtended
would overshoot the OUTPUT FREQUENCY FACTOR

range, indicating that saturation is likely.

3.2.7

Sweep Operation

For sweep operation, set up the generator for con-

tinuous operation (refer to paragraph 3.2.1). The fre-
quency setting will be the lower frequency of the con-
tinuously varying (or swept) frequency. Switch

FM/SWP to internal or external modulation as desired.
If internal set the modulation generator FUNCTION

OUTPUT

MAIN DIAL

MOD

EXT

FREQUENCY

SETTING AMPLlTUDE

MOD IN

FACTOR*

1.8.

1.6-

.8-

.6-

.4-

.2-

.002-

.6

.8

1.6

1.8

*Multiply by FREQ MULT for actual output.

Figure 3-4. Frequency Modulation Nomograph

switch to SWP SET, monitor the FUNCTION OUT with
a counter or oscilloscope and vary the MOD
AMPLITUDE control for exactly the upper frequency
desired. Note that the main generatoris limited in fre-
quency range (limited to approximately the dial range
for any given multiplier setting). Select either/l/l for

sweep up

 for sweep down. Select the sweep

rate desired. Keep in mind

frequen-

cies are double the indicated frequencies on the

FREQ/PERlOD control.

Example 2 shows the output being swept from the

bottom of the range to midrange by setting the main
dial fully cw and the VERNIER fully ccw for absolute
bottom of the range. The MOD AMPLITUDE control
was left at midrange and the ramp 

) waveform

used as the modulator. The ramp is a positive going
only waveform. Had a balanced waveform been used,
the angle subtended would have included the dotted
line and resulted in saturation. If an external modula-
tion signal is to be used, the EXT MOD IN values in the
nomograph indicate the signal level required for the
desired results.

3-5

Summary of Contents for 148A

Page 1: ...NS INFORMATION PRO PRIETARY TO WAVETEK AND IS SOLELY FOR IN STRUMENT OPERATION AND MAINTENANCE THE INFORMATION IN THIS DOCUMENT MAY NOT BE DUPLICATED IN ANY MANNER WITHOUT THE PRIOR APPROVAL IN WRITIN...

Page 2: ...r is quiescent until trig gered by an external signal then generates one cycle at the selected frequency External Gate Same as external trigger except gen erator oscillates at the selected frequency f...

Page 3: ...m Inoperative at frequency multiplier settings below 100 Input frequencies roll off at 6 dB octave above one half of full range frequency and above 150 kHz Input impedance is IO 1 2 1 4 Frequency Rang...

Page 4: ...1 2 2 2 Frequency Range 0 1 Hz to 100 kHz in three 100 1 ranges Sweep 0 2 Hz to 200 kHz 2 x setting and are fixed level 10V p p balanced about ground M and M are fixed level 5 Vp from 0 to 5V 1 2 2 4...

Page 5: ...is quiescent until a proper gate signal is applied at the EXTTRIG IN BNC 13 and then outputs the selected signal for the duration of the gate signal plus the time to complete the last cycle generated...

Page 6: ...red One cycle of waveform for each trigger signal C Gated A burst of waveforms for the dura tion of each gate signal d AM The instantaneous amplitude of the out put signal varies with the instantaneou...

Page 7: ...r gating the generator For manually triggering single cycles the generator mode should be EXT TRIG with no external signal in put at the EXT TRIG IN connector Each time TRIG GER LEVEL is rotated cw th...

Page 8: ...ing decreases and the angle subtended in the nomograph decreases If the MOD AMPLITUDE control is rotated toward MAX the angle subtended would overshoot the OUTPUT FREQUENCY FACTOR range indicating tha...

Page 9: ...red One cycle of waveform for each trigger signal C Gated A burst of waveforms for the dura tion of each gate signal d AM The instantaneous amplitude of the out put signal varies with the instantaneou...

Page 10: ...r gating the generator For manually triggering single cycles the generator mode should be EXT TRIG with no external signal in put at the EXT TRIG IN connector Each time TRIG GER LEVEL is rotated cw th...

Page 11: ...ing decreases and the angle subtended in the nomograph decreases If the MOD AMPLITUDE control is rotated toward MAX the angle subtended would overshoot the OUTPUT FREQUENCY FACTOR range indicating tha...

Page 12: ...per Limit 2 0 x FREQ MULT Lower Limit 0 001 X Upper Limit Nominally the phase of the main generator is shifted ten degrees for each volt of instantaneous modulation signal When the main generator is s...

Page 13: ...and the hysteresis switch goes to 2V This switches currents at the diode gate and the negative going triangle slope is started When the triangle reaches the 1 25V limit the hysteresis switch will swit...

Page 14: ...con tinuous independent of generator mode While the integrating capacitor is being held from charging the start stop diode must sink the current source which has a magnitude variable with VCG in puts...

Page 15: ...across series resistors to the supplies equal to the control voltages The FET currents will be switched at the diode gate into a timing capacitor to produce the triangle waveform 4 2 2 Symmetry Contr...

Page 16: ...R 9 VERNIER I R 2 1 R SYMMETRY R R 2 OM R 9 Figure 4 3 VCG Simplified Schematic...

Page 17: ...th output impedance low enough to drive the hyster esis switch and the triangle buffer In series with Q8 is a matched duplicate FET Q9 Q9 has the identical drain current as Q8 and therefore the same g...

Page 18: ...circuit In the positive pulse mode the square wave rather than the triangle wave is fed to the circuit and the 15 volt power is switched off As a result the negative swing of the input square wave is...

Page 19: ...ter current The result is that the voltage at point B I N P U T U 19 Q37 Q38 r which is the output voltage will start to go negative Finally when the output has moved far enough negative to pull point...

Page 20: ...ve than the trigger level is 4 8 clipped by forward biasing CR1 the negative portion is clipped by CR2 While CR1 is on Q1 conducts and Q3 switches off to a TTL low level While CR2 is on Q1 is off and...

Page 21: ...erefore R64 will have the same voltage across it as the drop across CR2 The current leaving Q7 enters the trigger amplifier summing node and becomes a voltage offset equal to the drop across CR2 becau...

Reviews: