background image

3 of 23

WX-501-0552 • 01.22

Installation and Wiring

Before you install and wire your Click 111, it’s important to understand how the buses and channels work. As 

mentioned above, the Click 111 has two RS-485 buses, each of which can be connected to one sensor. Sensors 

can be connected to these buses via the RJ-11 jacks on the faceplate; each bus has two RJ-11 jacks. It’s also fine to 

connect a single sensor to the Click 111, but for the most part we’ll assume that two sensors will be used.

Also as mentioned above, the Click 111 is a 16-channel card: it can output 16 channels of contact closures to the 

Swarco controller. These 16 channels are distributed between the two RS-485 buses. By default, they are evenly 

distributed: bus 1 has eight output channels assigned to it, and bus 2 has the other eight output channels assigned 

to it. (This would mean that each sensor can get eight channels’ worth of data to the Swarco controller.)

However, using configuration options on the Click 111, you can change the distribution of the channels. It must 

always be in increments of two, allowing the following combinations:

Sensor 1

Sensor 2

16

0

14

2

12

4

10

6

8

8

6

10

4

12

2

14

0

16

Note. 

Changing the allocation of the output channels will be covered later.

So as long as one of these options suits your needs for output channels, using a single Click 111 as outlined below 

will work just fine.

1.  If you’re using hardware configuration, set all DIP switches before installing Click 111 devices (this will be 

covered in the DIP Switches section).

2.  Insert the card into the rack.
3.  Connect a patch cable from one of the RJ-11 jacks labeled Bus 1 on the faceplate of the device to the surge 

protector (Click 200, 222 or 223) being used for one of your two sensors.

4.  Connect a second patch cable to one of the RJ-11 jacks labeled Bus 2 to the surge protector being used for 

your second sensor.

But what do you do if both of your sensors need more than eight channels, and therefore none of the options in the 

bulleted list above suit your needs? In that case, your easiest option will be to use one Click 111 card per sensor.

1.  If you’re using hardware configuration, set all DIP switches before installing Click 111 devices (this will be 

covered in the DIP Switches section).

2.  Insert two cards into the rack.
3.  Connect a patch cable from one of the RJ-11 jacks on the faceplate of the first Click 111 to the surge protector 

(Click 200, 222 or 223) being used for one of your two sensors.

4.  Connect a second patch cable to one of the RJ-11 jacks on the faceplate of the second Click 111 to the surge 

protector being used for your second sensor.

Summary of Contents for Click 111

Page 1: ...thers 9600 5 6 7 8 1 2 3 4 0 0 0 0 SW 0 0 0 1 1 0 0 1 0 3 0 0 1 1 5 0 1 0 0 7 0 1 0 1 9 0 1 1 0 11 0 1 1 1 13 1 0 0 0 15 5 6 7 8 1 2 3 4 1 0 0 1 17 1 0 1 0 19 1 0 1 1 21 1 1 0 0 23 1 1 0 1 25 1 1 1 0...

Page 2: ...of the device as follows Yellow RD Lights up when the Click 111 is receiving data on any port Green TD Lights up when the device is transmitting data on any port Blue MF This LED indicates whether the...

Page 3: ...put channels will be covered later So as long as one of these options suits your needs for output channels using a single Click 111 as outlined below will work just fine 1 If you re using hardware con...

Page 4: ...vered in the DIP Switches section 2 Insert two cards into the rack 3 Connect a patch cable from one of the RJ 11 jacks labeled Bus 1 on the faceplate of the first Click 111 to the surge protector Clic...

Page 5: ...onnection A6 No connection A7 Fault Status Out A8 No connection A9 DC common A10 No connection A11 DC common A12 Channel 5 normally open A13 No connection A14 DC common A15 Channel 9 normally open A16...

Page 6: ...ing multiple configuration methods and some of them can only be set using one particular method The table below lists how each parameter may be accessed and configured DIP Switch Front Panel Menu Clic...

Page 7: ...to choose between Hardware Software modes If Software mode is selected the parameter must be configured using the front panel menu or Click Supervisor If Hardware mode is selected the parameter can b...

Page 8: ...he front panel menu will be able to display the current setting but not change it If all switches are off down Software mode is selected and only Click Supervisor and the front panel menu will be able...

Page 9: ...the current setting but not change it If all switches are off down Software mode is selected and only Click Supervisor and the front panel menu will be able to both display and change the current set...

Page 10: ...know a bus will not be receiving any data for instance if you re only using one sensor with your Click 111 If a bus is disabled from receiving data then its associated channels will not go into a faul...

Page 11: ...e front panel menu will be able to both display and change the current setting Warning If you don t have switch 1 on flipped up to set it to Hardware mode anything you set on switches 2 and 3 will be...

Page 12: ...bank will be referred to as Level 2 and is used in configuring the menu options Mode Menu RD TD MF PWR 1 2 3 4 Detection 1 4 5 8 9 12 13 16 Note The multicolored LEDs also function as activity status...

Page 13: ...hes As shown above the menu options are displayed on the Level 1 LEDs and the configuration parameters are displayed on the Level 2 LEDs If a configuration parameter has been set using the DIP switche...

Page 14: ...bled Bus 1 Data Enabled Bus 2 Data Disabled Bus 1 Data Disabled Bus 2 Data Enabled Bus 1 2 Data Enabled Default LED off Cancel and exit menu LED on See the Navigating through the Menu and the Menu Ope...

Page 15: ...ud rate for bus 1 Level 2 LEDs 9600 bps default 19200 bps 38400 bps 57600 bps LED off Cancel and exit menu LED on Navigating through the Menu and the Menu Operation Example sections for how to configu...

Page 16: ...ey are set to Hardware the front panel menu will be able to display but not change these settings Channel Allocation The next parameter on the front panel menu label is channel allocation To select th...

Page 17: ...an also be changed using the DIP switches or Click Supervisor This parameter lets you choose the polarity of the calls placed by the Click 111 A call can be indicated by either high voltage or low vol...

Page 18: ...d red LEDs come on solid Note This parameter can also be changed using the DIP switches or Click Supervisor This parameter lets you choose whether the device will go into a fault state at all If fault...

Page 19: ...the Navigating through the Menu and the Menu Operation Example sections for how to view this parameter After the Click 111 has reset to factory defaults it will check the DIP switches if any of them a...

Page 20: ...ation about your device The tab has the following parameters see the figure and table below Note This parameter can only be configured using Click Supervisor Setting Description Module Allows you to e...

Page 21: ...e and table below Note These parameters can also be configured using the DIP switches or the front panel menu if in the DIP switches they are set to Hardware mode the parameters will appear grayed out...

Page 22: ...is low or high when the output is asserted Chan Out Polarity Lets you choose the polarity of the output channels whether the voltage is low or high when there is a call on that channel Fault Enable Le...

Page 23: ...ve your settings return to the Select Driver screen and more The Save menu allows you to save your settings Select Save to File to save your settings to a file Selecting this will open a directory box...

Reviews: