25
Shift 3 Start
EP
The time that shift 3 operations start, to help the system perform shift based operations, formatted as
HH:MM in 24 hour format, e.g. 24:00. If the update fails, modify your entry to match the HH:MM format
and try again.
Freq Call TH
EP
The minimum time, in minutes, between the time of deactivation of a call for a particular sensor and
reactivation of that call, at which that call should be marked as a frequent call, for use in the Frequent
Calls report
Slow Resp TH
EP
The minimum time, in minutes, between the time of activation of a call for a particular sensor and
deactivation of that call, at which that call should be marked as a slow response call, for use in the
system reports. The Slow Response Threshold is also used to determine when to route the active call to
any defined Backup Zones, or if no Backup Zones are defined for the affected zone, to determine when
to escalate the active call to supervisory level. A value of 0 indicates that this feature is disabled.
Backup Resp TH
EP
The Backup Response Threshold is used to determine when to escalate an active call to supervisory
level, after that call has been routed to any defined Backup Zones. A value of 0 indicates that this
feature is disabled.
Sec/Repeat Paging
EP
The time, in seconds, that should occur between radio paging based repeat notifications of an active
alert. Applies to both POCSAG and audio file based radio paging.
Page Cancel
EP
When checked, radio paging output includes a cancel notification when an alert is deactivated. This
setting is only applied within the event processing system. Cancel notification can also be configured for
each Data Output in the data output’s Settings field.
Default Zone
EP
The Zone that newly detected sensors should be auto-assigned to. If Unassigned is selected, newly
detected sensors will not be auto-assigned to a Zone. Selecting a Default Zone makes zone to wireless
receiver assignments and zone to sensor assignments much easier to accomplish due to the auto-
assignment process.
Include Location
When checked, alert notification text will include information defining the location where the alert was
generated, for sensors that can be mobile.