Monitoring dew point via relative humidity
sensor of room thermostat
Every DRT-200 room thermostat has a built in relative humidity
sensor. Take care removing the white-yellow part on the
thermostat to make it works.
The WTC-3 base unit continuously receives the actual relative
humidity and room temperature data from every room thermostat.
The built in program can calculate the actual dew point tempera-
ture from these data in every room. When the dew point reaches
a predefined level, the base unit will adjust the room thermostat
to a higher temperature to prevent the
condensation. This gives the highest level of comfort and the
optimum cooling capacity.
5.4.2.
Connect dew point sensor to DRT-200
room thermostat
An override dew point sensor should be connected directly to the
DRT-200 room thermostat.
Two (2) types of dew point sensor can be connected :
Dew point sensor for dry system
Dew point sensor for wet system
This sensor must be placed in the ceiling next to the inlet pipe.
The sensor has 10m of wire that can be connected directly to the
first and second input of DRT-200. The dew point sensor also
monitors condensation in addition to the built in relative humidity
sensor.