Wavin Temp Manifold Installation Manual
ower
info@wavin.com
www.wavincom
.
TELEPHONE
+31(38)429411
32
Wavin Temp Control Manual
ower
info@wavin.com
www.wavincom
.
TELEPHONE
+31(38)429411
8
8..4
4 R
Re
eg
giis
stte
err ((o
on
nlly
y rre
ea
ad
da
ab
blle
e))
Address
Description [unite]
Value
4121
Water temperature (WTC 43/44-input) [0.1 °C]
0..1000
4122
1. DWP resistance [kohm]
100..20000
4123
2. DWP resistance [kohm]
100..20000
4124
3. DWP resistance [kohm]
100..20000
4125
4. DWP resistance [kohm]
100..20000
4126
5. DWP resistance [kohm]
100..20000
4127
Relative humidity [0.1%]
10..1000
4128
RH temperature [0.1 °C]
0..500
4132
PI output [0.1%]
0..1000
4133
Dew point [0.1 °C]
0..500
4134
Type of unit (DIP4)
0..15
4136
TH1 measured temperature [0.1 °C]
0..500
4137
TH1 humidity [0.1 %]
0..1000
4138
TH1 calculated dew point [0.1 °C]
0..500
4139
TH1 pot meter [0.1 °C, +/- sign]
-max..+max
4140
TH1 DWP resistance [kohm]
0..20000
4141
TH1 brightness [lux]
100..1000
4142
TH2 measured temperature [0.1 °C]
0..500
4143
TH2 humidity [0.1 %]
0..1000
4144
TH2 calculated dew point [0.1 °C]
0..500
4145
TH2 pot meter [0.1 °C, +/- sign]
-max..+max
4146
TH2 DWP resistance [kohm]
0..20000
4135
Status of control
0: Initialization (onl after turn on)
1: Heating
2: Cooling
3: Heating / Cooling changeover
0..3
4147
TH2 brightness [lux]
100..1000
4148
TH3 measured temperature [0.1 °C]
0..500
4149
TH3 humidity [0.1 %]
0..1000
4150
TH3 calculated dew point [0.1 °C]
0..500
4151
TH3 pot meter [0.1 °C, +/- sign]
-max..+max
4152
TH3 DWP resistance [kohm]
0..20000
4153
TH3 brightness [lux]
100..1000
Design Manual
TELEPHONE
+31 (38) 4294911
4
info@wavin.com
www.wavin.com