background image

 

 
 
 

 

 

© Copyright  

2008-03-20  V0  Rev.01.0

 

- 18 - 

WT004139 

 

HYDRAULIC COMPONENTS 

 
 

Manual ball valve 

The manual ball valve is on the dispenser inlet and prevents the entrance of natural gas in the dispenser itself 
during any maintenance operations. 
This valve is normally installed on a system when a dispenser is also installed. 

   

Particulate filter 

The particle filter is on each inlet line of the dispenser and its function is to separate any solid particles from 
the  compressed  natural  gas  in  order  to  optimize  gas  flow  and  avoid  particle  deposits  in  the  internal 
components.  

  

Check valve 

The check valve’s function is to prevent gas flow in the opposite direction of dispensing. 

 

Mass-flow meter 

The  CNG  dispensers  are  equipped  with  mass-flow  meters  that  rely  on  the  Coriolis  effect.  The  mass-flow 
meter measures the quantity of gas dispensed and communicates with the electronic head. 
 
 

 

Coriolis  effect:  a  force  apparently  due to the speed of rotation of a non-inertial  reference system 
compared  to  an  inertial  reference  system;  it  is  equal  and  opposite  to  the  product  of  the  mass  of 
particles on which it acts and the relative Coriolis acceleration   

 
For  operating  characteristics  and  more  information  regarding  the  mass-flow  meter,  refer  to  the  specific 
technical manuals. 
 
 

Motorized valve 

The motorized valve includes a ball valve, a solenoid and a pneumatic actuator. 
When the dispensing selector is switched to the ON position (dispensing), the head sends a command to the 
solenoid, which activates the inlet of compressed air into the actuator through the inlet door; at this point the 
ball valve opens and the gas starts to flow. 
The motorized valve returns to its initial position when the head sends the inverse command to the solenoid, 
which activates the inlet of compressed air through the outlet door; in this case the ball valve closes and the 
flow of the gas stops. 

 

Pressure gauge 

The CNG dispenser has a pressure gauge with a scale division from 0 to 400 bar, which allows a constant 
monitoring of gas pressure. 

 

Delivery hose 

The CNG dispenser’s filling hoses are specifically designed and manufactured to supply natural compressed 
gas.   
The hoses are wear proof and are high-performance. 
There are twin hoses for dispensing and venting. 
Standard hoses have an internal diameter of ¼ inch (standard flow) or ½ inch (high flow) 

 

Delivery Nozzle  

The  CNG  dispenser  has  nozzles  capable  of  satisfying  all  the  requisites  of  efficiency  and  safety  related  to 
CNG fuelling. 
Generally there are two types of nozzles, for light vehicles (used to fuel automobiles, vans and small trucks) 
or nozzles for heavy vehicles (used to fuel buses and trucks). However, there are different nozzles, according 
to the characteristics required by different CNG systems (Italy type, NGV1 type, NGV2 type etc). 
 

 

Summary of Contents for GLOBAL VISTA CNG

Page 1: ...EN WT004139 2008 03 20 V0 Rev 01 0 Global Vista CNG Instruction Manual ...

Page 2: ...ния перед началом любых работ Warning Never run a leaking pump Be careful with the environ ment and mind the skidding risk take care of leaking fuel immediately Varning Använd aldrig en läckande pump Tänk på miljön och halk risken sanera utläckt driv medel snarast Warnung Lassen Sie nie eine undichte Zapfsäule laufen Seien Sie umweltbewusst und denken Sie an die Rutschgefahr beseitigen Sie austret...

Page 3: ...stallation 9 Initial start up 16 Dispensing procedure 16 COMPONENTS 17 Hydraulic components 17 Electrical components 17 HYDRAULIC COMPONENTS 18 Manual ball valve 18 Particulate filter 18 Check valve 18 Mass flow meter 18 Motorized valve 18 Pressure gauge 18 Delivery hose 18 Delivery Nozzle 18 Three way valve 19 Breakaway Device 19 ELECTRICAL COMPONENTS 19 Electronic head 19 Electrical components u...

Page 4: ...Dresser will not be held responsible for any tampering performed by the customer who in this case will be the only party held liable by the competent authorities For further information on the main components of the equipment mass flow meter actuator board etc and or original spare parts see the specific technical documentation given to your technical assistance after sales company Warnings for fu...

Page 5: ... positions of these warnings depend on local conditions but they must be visible from the dispenser Ensure that all station attendants know how to behave in an emergency situation Protection from pressure related risks The hydraulic circuit of the dispenser works under pressure Before performing any maintenance accurately close the cut off valve s located at the base of the dispenser and release t...

Page 6: ...e prohibit or restrict access to the switches used to interrupt power supply to the dispenser Ensure that the fuelling station has both an electrical line equipped with an automatic breakaway device as well as a proper grounding system in compliance with all applicable regulations Dispenser Identification The GLOBAL VISTA CNG dispenser can be manufactured in different versions due mainly to the di...

Page 7: ...the mass flow meter in the dispenser The information given by the mass flow meter or any other sensors temperature sensor pressure sensor etc are processed by the electronic head which carries out specific operations based on the values it receives The CNG dispensers can be Single stage dispensers that control a single valve first stage level their hydraulic system communicates with one storage ta...

Page 8: ...the areas indicated with the arrows in this diagram areas are about 50 cm one from the other Always use the proper methods to lift and transport the dispenser Non compliance with the instructions for moving the dispenser could cause serious damages to things and people Once you have received the dispenser carefully inspect the equipment to ensure that it has not been damaged during transportation ...

Page 9: ...tem normally composed of an emergency button and one or more safety switches that is capable of interrupt the flow to the equipment in case of operating problems The emergency stopping system not included with the dispenser must comply with national regulations for example EN 60204 1 The safety device must be placed in the gas station in order that it is easily accessible to attendants Following a...

Page 10: ... Copyright 2008 03 20 V0 Rev 01 0 10 WT004139 ...

Page 11: ... Copyright 2008 03 20 V0 Rev 01 0 11 WT004139 ...

Page 12: ... Copyright 2008 03 20 V0 Rev 01 0 12 WT004139 ...

Page 13: ... Copyright 2008 03 20 V0 Rev 01 0 13 WT004139 ...

Page 14: ... Copyright 2008 03 20 V0 Rev 01 0 14 WT004139 ...

Page 15: ... Copyright 2008 03 20 V0 Rev 01 0 15 WT004139 ...

Page 16: ... by dispensing some gas following the procedure indicated in the following paragraph Check the meter s calibration by dispensing gas a few times and comparing the measurements given by the electronic head with those given by a proper sampling instrument For Example precision scale Dispensing procedure To dispense CNG follow these procedures remove the nozzle from its housing connect the nozzle to ...

Page 17: ... and electrical components External components 1 Lower front panel 2 Column 3 Nozzle Housing 4 Computing Head Housing 5 Cover 6 Base 7 Id plate Hydraulic components 8 Manual ball valve 9 Particulate filter 10 Check valve 11 Mass flow meter 12 Motorized valve 13 Pressure gauge 14 Delivery hose 15 Delivery Nozzle 16 Breakaway Device Electrical components 17 Electronic head 18 Pressure transmitter 19...

Page 18: ...he motorized valve includes a ball valve a solenoid and a pneumatic actuator When the dispensing selector is switched to the ON position dispensing the head sends a command to the solenoid which activates the inlet of compressed air into the actuator through the inlet door at this point the ball valve opens and the gas starts to flow The motorized valve returns to its initial position when the hea...

Page 19: ...damages to persons the dispenser and the vehicle ELECTRICAL COMPONENTS Electronic head Description The CNG dispenser is equipped with a Dresser electronic head which guarantees high performance in calculating and constantly monitoring all the operations carried out by the dispenser The head designed specifically to manage CNG dispensers performs the following operations management and control of t...

Page 20: ...NTENANCE The dispenser leaves the factory only after passing accurate tests hydraulic and electrical A correct installation and use should guarantee proper functioning In any case in order to maintain the dispenser s optimal conditions in time and guarantee its safety the station manager must check the components listed in the table below periodically Component Intervention Pneumatic actuator Peri...

Page 21: ... remember to disconnect the power supply before operating on the components of the CNG dispenser Cleaning To clean the dispenser do not use abrasive detergents or products petrol petroleum based products Instead use water with non aggressive detergents and soft cloths Adopt all necessary precautions to avoid any water entering the dispenser Before entering the head box carefully dry any traces of ...

Page 22: ...ens while the volume display will show the pre established unit price for example 1 235 0 1 235 1 235 For example pressing P0 once and P1 twice the display will appear as follows 2 1 235 Pressing P0 again another digit is added on the display and it can be increased or decreased by pressing P1 or P2 respectively 20 1 235 The same applies when setting the next digits If the new price is set the dat...

Page 23: ...an be set with the P001 parameter Values are 0 e 1 0 manual mode 1 automatic mode Warning if the dispenser is connected to the Host it will shift into automatic mode even if it is set to manual Further information For further information regarding programming operation and the meaning of certain error codes displayed by the electronic head refer to the related manual ...

Page 24: ... Year of construction 3 Type of product 4 Space for directions 5 II 3 G group II surface category 3 potentially explosive atmosphere due to presence of gas vapors or fog 6 CE marking in compliance with EMC and ATEX 7 Epsilon X marking in compliance with the ATEX directive 8 Name and address of the manufacturer 3 1 2 ID PLATE 4 5 6 7 8 ...

Page 25: ... Copyright 2008 03 20 V0 Rev 01 0 25 WT004139 DECLARATION OF CONFORMITY ...

Page 26: ...____________________________________ _________________________________________________________________________________________ _________________________________________________________________________________________ _________________________________________________________________________________________ _________________________________________________________________________________________ ___...

Page 27: ...V0 Rev 01 0 27 WT004139 MARKET SERVICE To obtain name and address of the closest authorized maintenance company please contact DRESSER WAYNE DRESSER Italia S r l Via Roma 32 23018 TALAMONA SO Tel 0342 608111 Fax 0342 608299 ...

Page 28: ...n with overall responsibility to the customer Field service technical support and supply of spare parts Ausrüstungen wie Zapfsäulen Zahlterminals Kassenterminals und Tankstellensysteme Software für Registrierung und Kommunikation auf der Tankstelle u zwischen Station und Mineralölfirma sowie Banken und Kreditinstituten Projektgestaltung mit umfassender Verantwortlichkeit dem Kunden gegenüber Servi...

Reviews: