GRANUDOS S5, control unit
Index: 02
Date modified: 11/05/2021
OI No.: BA SW 014-02 Granudos S5-Steuereinheit EN.docx
Page 19 of 29
Main menu
Service
Output test
The output test is used to check the connected outputs (actuators and relays). The selected output is activated
for 20 seconds. The activation can be cancelled at any time using “Enter”.
For safety reasons (generation of chlorine gas), the output test for the chemical-dosing outputs is only released
if no fault exists that could prevent the dosing, e.g., flow in the suction pipe too low.
An output test can be performed for the following actuators:
1.
pH (=acid) dosing
2.
Chlorine dosing
3.
Knocker - 4x active
4.
Heating
5.
Actuator dust extraction (optional)
6.
flushing valve dust extraction (optional)
7.
Fault indication with relay output
8.
pH (=acid) empty = output test for indication with relay output
9.
Chlorine empty = output test = indication with relay output
Main Menu
Service
Info
The software version used can be viewed using the Info button.
This is required for support queries.
Main menu
Event log (event and data logging)
The Event log displays the past 25 fault indications. Use the arrow keys to scroll up and
down. The last fault indication received is in the no. 1 position.
At the end of the list, the “Delete log?” command is shown under no. 26. Use “Yes“ to
delete the entire list.
Back to the main menu using the “Shortcut” (Chapter 6.1)
Actuat dust