CPR Touch XL, Control Unit
Index: 03 Date modified: 22/06/2022
OI No.: BA MR 001-03 Steuereinheit CPR Touch XL EN.docx
Page 24 of 70
6.1.2
Automatic operation
The device is in “automatic” operating status. The auxiliary
hygiene parameters and the temperature are regulated based
on set parameters.
There is no fault.
The
Out list
shows the currently active outputs and/or
actuators as an example.
6.1.3
Quick Info
In automatic operation, the set control parameters can be
viewed quickly and without a password prompt via the “Quick
Info” function by touching the corresponding symbol.
Quick Info is only used for querying the control parameters;
no changes can be made.
6.1.4
Start - Dosing delay
If the device is restarted, the dosing delay is running; during
this time, no dosing output is activated.
Software alarms are suppressed during this time.
The dosing delay must be set high enough to ensure that after
the start of the filter system actual basin water flows through
the measuring cell.
The dosing delay can be cancelled with
and the device is
set to automatic operation.
6.1.5
Automatic – Startup
If one of the two measuring values pH or Cl falls outside the
control range, the “Startup” start routine is activated.
During the start routine, the dynamic dosing time monitoring
is active. If the measuring value does not reach the control
range within the selected time, e.g., due to a malfunction or
too low dosing performance, the dosing stops with an alarm.
The dosing time monitoring alarm is signalled by
. This
fault can only be reset through a device restart or a manual
acknowledgement.