2
3
ATTACHMENT TO NON-STRUCTURAL WALLS
When attaching to walls that are not structural walls, a post system is used instead of a wall mount
bracket. The wall post is attached to the wall, but the anchors used to attach it do not bare any load.
Their purpose is simply to brace the post against the wall, while the load is borne by the post itself. In
other words, the load is transferred down the post and is absorbed by the floor.
LOAD TESTING
After the installation is complete, the system must be load tested to 125% of the maximum load stated
on the label of the ceiling lift.
To measure track deflection, only 100% of the SWL is used. The track may only deflect 1” for every 200”
of unsupported track (1:200 ratio)
After the load test has been completed, the Final Inspection Checklist but be filled out.