background image

Compressor Replacement and System Service

Webasto Product N.A., Inc.

36

www.techwebasto.com

7. Compressor Replacement and 

System Service

7.1

System Cleanup and Compressor 
Replacement After Compressor 
Failure

Once you determine that a compressor needs to be 
replaced you must then determine whether the system 
has been contaminated.  Compressor motor failure can 
lead to such contamination.  (While compressor motor 
failure is sometimes referred to as motor “burnout”, it 
does not mean that a fire actually occurs inside a 
hermetic compressor.)  Even small amounts of 
contamination must be removed from the system to 
avoid damaging the replacement compressor.  Therefore, 
it is important to thoroughly clean a refrigeration/air 
conditioning system if system contamination is present.

If a compressor motor failure has 
occurred, refrigerant or mixtures of 
refrigerant and oil in the system can be 
acidic and cause chemical burns.

As always, to avoid injury, wear appropriate protective 
eye wear, gloves and clothing when servicing an air 
conditioning or refrigeration system.  If refrigerant or 
mixtures of refrigerant and oil come in contact with skin 
or eyes, flush the exposed area with water and get 
medical attention immediately.

The following outlines a process for compressor 
replacement and system clean-up for a system equipped 
with a Tecumseh compressor.  You should refer to the 
original equipment manufacturers (OEM) service 
information.

A. Determine Extent of System Contamination

Following the precautions in “Refrigerants and Other 
Chemicals” and “Compressor Removal” on page 27, 
remove the compressor.

Use the following guidelines to determine whether 
contamination, if any, is limited to the compressor or 
extends to the system.

If the discharge line shows no evidence of contamination 
and the suctions tub is clean or has only light carbon 
deposits, then the contaminants are limited to the 
compressor housing (Compressor Housing 
Contamination).  A single installation of liquid and 
suction line filter-driers should clean up the system.

If, however, the discharge line or the suction line shows 

evidence of contamination, the compressor was running 
at the time of the motor failure and contaminants were 
pumped throughout the system (System Contamination).  
If System Contamination has occurred, several changes 
of the liquid and suction line filter-driers will be needed 
to cleanup the system.  In addition, the thermal 
expansion valve will need to be replaced.

B. Install Replacement Compressor and 

Components

1. Install the replacement compressor with new 

external electrical components (capacitors, relay, 
overload, etc., where applicable).

2. Install an oversized liquid line filter-drier.

3. Install a generously sized suction line filter-drier 

immediately upstream of the compressor.  The drier 
when permanently installed in a clean system must 
have a pressure drop not more than 2 psi, or initially 
installed in a dirty system temporarily, must have a 
pressure drop not more than 9 psi.  Pressure taps 
must be supplied immediately before and after the 
suction filter-drier to permit the pressure drop to be 
measured.

If a suction line accumulator is present and System 
Contamination has occurred, it must be thoroughly 
flushed to remove any trapped sludge and thus 
prevent if from plugging the oil return hole.  The 
filter-drier should be installed upstream of the 
accumulator and the compressor.

In case of Compressor Housing Contamination, the 
filter-drier should be installed between the 
compressor and the suction line accumulator.

Rubber refrigeration hoses are not satisfactory for 
temporarily hooking up the suction line filter-drier to 
the system since the acid quickly breaks down the 
rubber and plastic.

4. Follow the Precautions in “System Flushing, Purging, 

and Pressure Testing for Leaks” on page 28, to purge 
the system and pressure test for leaks.

C. Evacuate the System

Evacuate the system to less than 1000 microns, using a 
good vacuum pump (not a compressor) and an accurate 
high vacuum gauge.  Operate the pump at 1000 
microns, or less, for several hours to be sure the vacuum 
is maintained.

Alternate method of removing moisture and non-
condensable material from the systems is:

WARNING

Summary of Contents for BlueCool Truck BCT010300A

Page 1: ...or repair a Webasto heating or cooling system unless you have successfully completed the factory training course and have the technical skills technical information tools and equipment required to pr...

Page 2: ......

Page 3: ...e 9 3 3 Discharge Mode Bunk Cooling 10 3 3 1 Vehicle Key OFF no 12V reference signal present at control module 10 3 3 2 Operation 10 4 Technical Data 11 4 1 General Information 11 4 1 1 Technical Data...

Page 4: ...ment and System Service 36 7 1 System Cleanup and Compressor Replacement After Compressor Failure 36 8 Circuit Diagrams 38 9 Component Replacement Refrigeration Unit 39 9 1 General Information and Saf...

Page 5: ...uation which if not avoided MAY result in minor or moderate injury or property damage It may also be used to alert against unsafe practices These symbols are used to alert the technician to important...

Page 6: ...s and services should be performed Trucks other than new will likely require additional services such as Cleaning of battery connections Cleaning of jumpers bottom of connector typical weak connection...

Page 7: ...r accessory kit The power inverter converts 12 volts DC supplied by the vehicle batteries into 110 volts AC required to drive the refrigeration compressor Where the vehicle is equipped with the option...

Page 8: ...ge 12 volts DC vehicle power into 110 volts AC is utilized to supply power to drive the electric refrigeration compressor Figure 6 Power Inverter 2 6 Control Module The control module is central to en...

Page 9: ...ature sensor s performance can only be analyzed through the use of a special tool available from Webasto Figure 8 Digital Core Temperature Sensor 2 8 Ambient Temperature Thermostat Located behind the...

Page 10: ...al Protector Hermetic Compressor Motor 110 VAC Device Lethal current may be present Switch off the DC to AC power inverter before servicing The compressor motor is protected from overheating by a ther...

Page 11: ...delayed start countdown after which based on the temperature in the storage unit WILL or WILL NOT provide a signal to the control relay Approximate time to completely recharge freeze the storage core...

Page 12: ...eration The chilled coolant mixture is circulated by way of a small coolant pump from the storage unit to the air handler unit heat exchanger in the cab and back to the storage unit The air handler fa...

Page 13: ...and cold storage assembly Cab mounted air chiller handler 300 lb 136 kg 26 lb 13 6 kg Storage System Design Maintenance free with patented graphite matrix no additional batteries required System Refri...

Page 14: ...ssembly Figure 14 Dimensions Refrigeration Cold Storage Assembly Specifications U 4846 Coolant Circulating Pump Flow rate against 0 0 PSI 0 0 Bar 528 g hr 2 000 l hr Rated Voltage 12 Volts Power Consu...

Page 15: ...w webasto us 13 Webasto Product N A Inc 4 2 2 Air handler Assembly Figure 15 Dimensions Air handler Assembly 179 8 mm 7 04 in 616 4 mm 24 26 in 623 6 mm 24 55 in 203 94 mm 8 03 in 498 5 mm 19 62 in 50...

Page 16: ...m in Charging Mode Vehicle Key ON or Vehicle Engine Running The following tables list the possible error symptoms If the actions listed in the following tables do not restore proper operation consult...

Page 17: ...30 minutes replace control module System control relay not responding Check 20 amp fuse at fuse holder X4 Check for power on pin 87 red wire and ground on pin 85 brown wire Refer to Fig 20 on pg 19 Ch...

Page 18: ...Fig 34 on pg 34 Check compressor function and electrical diagnosis Refer to Section 6 Troubleshooting Refrigerant Compressor Repair as necessary If open circuit OL replace limiter Repair or replace as...

Page 19: ...ve to Coolant Pump Purple 16GA 12V Switched Positive to Pressure Sensor X6 Ambient Thermostat X7 and System Control Relay X10 Not Used Black 20GA Storage Core Digital Temperature Sensor White 20GA Sto...

Page 20: ...Signal to Control Module Orange 14GA 12V Switched Positive to Coolant Pump Purple 16GA 12V Switched Positive to Pressure Sensor X6 Ambient Thermostat X7 and System Control Relay X10 Not Used Black 20...

Page 21: ...Circuit X10 X11 Blue 12GA 12V Switched Output to Condensor Fan X9 Brown 14GA Ground to Battery Negative Post Purple 16GA 12V Input from Control Module X1 Pressure Sensor X6 and Ambient Thermostat X7...

Page 22: ...from System Control Relay X10 On Off Switch Circuit to Power Inverter Not Used Viewed from wire insertion side LEGEND 87a 87 30 85 86 30 85 86 87 87a X11 OFF O N A C C Key Switch Position 30 min ON PO...

Page 23: ...ambient temperature thermostat Figure 24 Ambient temperature thermostat checks continuity Checking continuity through high low refrigerant pressure switch Figure 25 High low refrigerant pressure switc...

Page 24: ...ing condenser fan circuit Figure 27 Condenser fan circuit checks DC voltage DC TO AC POW ER INVERTER ON PO W ER OFF V AC Volts AC V _ Inverter ON Allumez l inverter To Refrigerant Compressor WARNING H...

Page 25: ...Replace blown defective fuse Damaged or open circuit Repair wiring or connections No ground connection Repair wiring or connections No output to circulation fans at control module With fan control tur...

Page 26: ...Constant Power Positive Fused 10 amp Brown 14GA Constant Negative to all Components Pink 16GA 12V Positive Reference Signal to Control Module Orange 14GA 12V Switched Positive to Coolant Pump Purple...

Page 27: ...ystem www webasto us 25 Webasto Product N A Inc Checking circulation pump circuit at pump Figure 30 Circulation pump circuit checks DC voltage V DC V V Volts DC _ To Circulation Pump To Main System Ha...

Page 28: ...ting these products should be done only by those with the necessary knowledge training and equipment Never service repair or troubleshoot unless you are a professional air conditioning refrigerationse...

Page 29: ...vere frostbite Also in the event of a compressor motor failure some refrigerant and oil mixtures can be acidic and cause chemical burns To avoid injury wear appropriate protective eye wear gloves and...

Page 30: ...sures in excess of 2000 PSIG at 70 F At pressures much lower than 2000 PSIG compressors can explode and cause serious injury or death To avoid over pressurizing the system always use a pressure regula...

Page 31: ...on of System Explosions In certain water utilizing refrigeration systems water can leak into the refrigerant side of the system This can lead to an explosion of system components including but not lim...

Page 32: ...trical problems a Compressor motor has a winding open or shorted b Start capacitor not working properly c Relay does not close See Identifying Compressor Electrical Problems on page 31 Same as a Same...

Page 33: ...power before removing the protective terminal cover Never energize the system unless the protective terminal cover is securely fastened and the compressor is properly connected to ground Never reset a...

Page 34: ...or a Hi Potential Ground Tester Hi Pot To reduce the risk of electrocution always follow the manufacturers procedures and safety rules when using these devices Connect one lead of either the megger or...

Page 35: ...C and S See Identification of Hermetic Terminal on page If there is no continuity replace the compressor See System Cleanup and Compressor Replacement After Compressor Failure starting on page 36 Chec...

Page 36: ...VAC White Ground Green Compressor Unit Ground Main Motor Winding Start Winding Compressor Housing Black Black White White Red Black Stripe Black DC AC Power Inverter Green Table 11 Troubleshooting PS...

Page 37: ...t services gauges to the system Turn on power to system If the system has an adequate refrigerant charge the compressor should maintain at least 200 psig pressure differential between the suction and...

Page 38: ...filter driers should clean up the system If however the discharge line or the suction line shows evidence of contamination the compressor was running at the time of the motor failure and contaminants...

Page 39: ...ermanent installation as described in Install Replacement Compressor and Components on page 36 On the other hand where Systems Contamination occurred an increased pressure drop will be measured Change...

Page 40: ...TOR 10 15VDC 120VAC 60HZ TEMPERATURE CURRENT LIMITER COMPRESSOR COOLANT PUMP CONDENSER FAN CONTROL UNIT IN AIR HANDLER X2 10A BATTERY BATTERY F3 KEY ON SIGNAL 12VDC BY INSTALLER 12V DC RELAY 12 VOLT C...

Page 41: ...rigerant from the system can cause a sudden release of refrigerant and oil Among other things this can Cause a variety of injuries including burns and frost bite Expose service personnel to toxic gas...

Page 42: ...d for R134a refrigerant systems 3 Disconnect refrigerant lines from condenser Protect open lines with plastic caps or wrap to prevent the ingress of moisture and contaminates 4 Remove the top plate ov...

Page 43: ...ess of moisture and contaminates 6 Remove the 2 allen head bolts securing the TXV to the storage core pipes 7 Pull the TXV free of the storage core pipes 8 Inspect TXV and lines for possible contamina...

Page 44: ...e replacement switch using a NEW O ring 6 Torque to specification 7 Apply an anti corrosive electrical grease to the terminals and connect to switch 8 Service system according to the precautions and r...

Page 45: ...te the ambient temperature switch It will be in the area of the compressor wire tied to the run capacitor Refer to Fig 42 4 Replace as required 5 Apply an anti corrosive electrical grease to the termi...

Page 46: ...rs from rotary switch shafts 3 Remove four screws holding panel to cover 4 Remove panel Installation 1 Reassembly in reverse order of removal 10 2 Air handler Cover Removal 1 Pull 10 amp fuse from fus...

Page 47: ...allation Before handling the new control unit discharge any possible static electrical charge from your body by touching a grounded metal surface 1 Reassembly in reverse order of removal 10 4 Fan Repl...

Page 48: ...Fig 49 item A DO NOT leave this valve open unattended 4 Continue to replenish the reservoir as coolant is drawn in 5 Continue to bleed air out at the bleeder valve until coolant is evident at the val...

Page 49: ...Reassembly in reverse order of removal AVOID DAMAGING HEAT EXCHANGER Lubricate heat exchanger connection tubes and coolant hoses with silicone spray before connecting hoses to heat exchanger 2 Refer t...

Page 50: ...Coolant Circuit Webasto Product N A Inc 48 www techwebasto com Figure 53 Circulating pump orientation 0 85 0 Correct Wrong...

Page 51: ...ation lack of reasonable and necessary maintenance alteration civil disturbance or act of God 8 Transportation damages should be claimed directly with the forwarding company 9 This limited warranty ap...

Page 52: ...Warranty Webasto Product N A Inc 50 www techwebasto com...

Page 53: ...Warranty www webasto us 51 Webasto Product N A Inc...

Page 54: ...duct N A Inc 15083 North Road Fenton MI 48430 Technical Assistance Hotline USA 800 860 7866 Canada 800 667 8900 www webasto us www techwebasto com Org 02 2007 Rev 2 2012 Ver BCT_ABC 2012 Webasto Produ...

Reviews: