101
CHAPTER 5 - START-UP
ACTION
LED DISPLAY
DESCRIPTION
LCD DISPLAY
Press the
Stop key
Press the
key and hold it
Release the
key
Motor decelerates down to 0 rpm
Motor accelerates from 0 rpm up to
the JOG speed set at P122
Ex
.: P122 = 150 rpm
CCW direction of rotation
Motor decelerates down to 0 rpm
VFD
ready
Motor
Speed
P002 = 150 rpm
VFD
ready
NOTE!
The last frequency reference value set via the
and
keys is saved.
If you wish to change this value before enabling the inverter, change parameter
P121
(Keypad Reference).
OBSERVATIONS:
(1)
If the rotation direction of the motor is not correct, switch off the inverter.
Wait 10 minutes to allow a complete discharge of the capacitors and then
swap any two wires at the motor output.
(2)
If the acceleration current becomes too high, specially at low frequencies
(< 15 Hz), adjust the Torque Boost at
P136
.
Increase/decrease the content of
P136
gradually until you obtain an
operation with constant current over the entire frequency range.
Refer to P136 in chapter 6.
(3)
If E01 fault occurs during deceleration, increase the deceleration time at
P101
/
P103
.