CHAPTER 6 - DETAILED PARAMETER DESCRIPTION
Range
[Factory Setting]
Parameter
Unit
Description / Notes
P044
0 to 65535
kWh Counter
[ - ]
1 kWh
Indicates the energy consumed by the motor.
Indicates up to 65535 kWh, then it returns to zero.
If P204 is set to 4, the P044 is reset to zero.
This value remains stored even when inverter is turned OFF.
P060
0 to 71
Fifth Error
[ - ]
Occurred
-
P061
0 to 71
Sixth Error
[ - ]
Occurred
-
P062
0 to 71
Seventh Error
[ - ]
Occurred
-
P063
0 to 71
Eighth Error
[ - ]
Occurred
-
P064
0 to 71
Ninth Error
[ - ]
Occurred
-
P065
0 to 71
Tenth Error
[ - ]
Occurred
-
Indicates the numbers of the fifth, sixth, seventh, eighth ninth and tenth
occurred error, respectively.
Record Systematic:
Exy
P014
P015
P016
P017
P060
P061
P062
P063
P064
P065
Ex: When the display show 0 (zero), this means E00, 1 (one) means
E01 and so on.
P070
0 to 2600
Current and
[ - ]
Motor Speed
0.1 A(< 100)
1 A(> 99.9)
0 to P134
[ - ]
1 rpm
Indicates simultaneously the motor current value (A) and the motor speed
value (rpm).
It is possible to use this parameter to change the speed reference (P121)
when P221 or P222 = 0.
NOTE!
The LED display shows the speed.
P071
LCD: 0 to 65535
Command Word
LED: 0 to FFFFh
Shows the command word value set through the network.
The LCD display of the keypad shows the value in a decimal
representation, while the LED display shows the value in a hexadecimal
representation.
P072
LCD: 0 to 65535
Fieldbus Speed
LED: 0 to FFFFh
Reference
Shows the speed reference value set through the Fieldbus network.
The LCD display of the keypad shows the value in a decimal
representation, while the LED display shows the value in a hexadecimal
representation.