173
CHAPTER 6 - DETAILED PARAMETER DESCRIPTION
P268
(1)
0 to 22
Digital Input DI6
[ 6 (Ramp 2) ]
Function
-
P269
(1)
0 to 22
Digital Input DI7
[ 0 (Not Used) ]
Function
-
(Located on the
optional board EBA
or EBB)
P270
(1)
0 to 22
Digital Input DI8
[ 0 (Not Used) ]
Function
-
(Located on the
optional board EBA
or EBB)
Range
[Factory Setting]
Parameter
Unit
Description / Notes
Parameter
P263
P264
P265
P266
P267
P268
P269
P270
Function
(Input)
(DI1)
(DI2)
(DI3)
(DI4)
(DI5)
(DI6)
(DI7)
(DI8)
Not Used
0
2 to 7
0, 7
0 and
0 and
0 and 0, 5, 7
0, 5
and 16
16
16
16
and 16 and 7
Start/Stop
1
-
-
-
-
-
-
-
General Enable
2
-
2
2
2
2
2
2
Fast Stop
3
-
-
-
8
8
8
8
FWD/REV
-
0
-
-
-
-
-
-
Local/Remote
-
1
1
1
1
1
1
1
JOG
-
-
3
3
3
3
3
3
No external Fault
-
-
4
4
4
4
4
4
Increase E.P.
-
-
5
-
5
-
-
-
Decrease E.P.
-
-
-
5
-
5
-
-
Ramp 2
-
-
6
6
6
6
6
6
FWD Run
-
-
8
-
-
-
-
-
REV Run
-
8
-
8
-
-
-
-
Speed/Torque
-
-
9
9
9
9
9
9
JOG+
-
-
10
10
10
10
10
10
JOG-
-
-
11
11
11
11
11
11
Reset
-
-
12
12
12
12
12
12
Fieldbus
-
-
13
13
13
13
13
13
Start (3 wire)
-
-
14
-
14
-
14
-
Stop (3 wire)
-
-
-
14
-
14
-
14
Multispeed (MSx)
-
-
-
7
7
7
-
-
Manual/Automatic
-
-
15
15
15
15
15
15
Motor Thermistor
-
-
-
-
-
-
-
16
Disables Flying
-
-
17
17
17
17
17
17
Start
DC Link Voltage
-
-
18
18
18
18
18
18
Regulator
Parameter Setting
-
-
19
19
19
19
19
19
Disable
Load User
-
-
20
20
20
20
20
-
Timer RL2
-
-
21
21
21
21
21
21
Timer RL3
-
-
22
22
22
22
22
22
Table 6.41
- Functions of the digital inputs
Notes about the Digital Inputs Functions:
-
Start/Stop -
To ensure the right actuation, this function needs
programming P224 and/or P227 = 1.
-
Increase E.P.
(Electronic Potentiometer) is active when DI3 or DI5 = +24 V.
Beyond parameters P265 and P267 = 5, it is also necessary setting P221
and/or P222 to 7.
-
Decrease E.P.
(Electronic Potentiometer) is active when DI4 or
DI6 = 0 V. Beyond parameters P266 and P268 = 5, it is also necessary
setting P221 and/or P222 to 7.
-
Local/Remote
= 0 V/24 V at the digital input, respectively.
-
Speed /Torque
is valid for P202 = 3 and 4 (Vector Control Sensorless
and Vector Control with encoder).