CHAPTER 6 - DETAILED PARAMETER DESCRIPTION
Range
[Factory Setting]
Parameter
Unit
Description / Notes
Figure 6.38 -
Diagram for the torque master/slave function
- F > Fx _ 1:
This function activates the relay and/or transistorized outputs
set to this option when the output frequency value (F) is greater than the
value set at P369 (Fx) plus the hysteresis value set at P370. When F <
Fx - P370, the outputs set to this option are deactivated (refer to figure
6.39 t)).
- F > Fx _ 2:
With this option the hysteresis for the acceleration is
disabled, therefore, this function activates the relay and/or transistorized
outputs set to this option when the output frequency value (F) is greater
than the value set at P369 (Fx). When F < Fx - P370, the outputs set to
this option are deactivated (refer to figure 6.39 v)).
- Set point = Process Variable.
This function activates the digital or
relay output when the Set point value equals the Process Variable value
(refer to figure 6.39 v)).
- No E32 -
It indicates that the inverter is disabled due to an E32 error.
- Ready 2
- Indicates that the motor is disabled (motor stopped) without
error and without undervoltage.
Symbols used in the Digital Output functions:
N
= P002 (Motor speed)
N*
= P001 (Frequency Reference)
Nx
= P288 (Speed Nx) - User selected speed reference point.
Ny
= P289 (Speed Ny) - User selected speed reference point.
Master
Slave
EBA.01
XC4:6
COM
XC4:4
DGND
XC4:8
24 Vcc
XC4:5
DO1 (/-)
R 500
3 W
XC1:17, 18
AO1
XC1:19, 20
AO2
CFW-09
EBA.01
EBA.01
XC1:10
GND
XC1:2
DI2 (FWD/REV)
XC1:12, 13
AI1 (Speed Reference)
XC1:15, 16
AI2 (Max. Torque
Current)
CFW-09
M
M