186
CHAPTER 6 - DETAILED PARAMETER DESCRIPTION
Range
[Factory Setting]
Parameter
Unit
Description / Notes
P285
0.0 to 300
Time for RL3 ON
[ 0.0 ]
0.1 s
P283
0.0 to 300
Time for RL2 ON
[ 0.0 ]
0.1 s
Used in the function as Relay Output: Timer of the relay 2 or 3.
When the timing function of the relays 2 and 3 is programmed at any
DIx, and when the transition is effected from 0 V to 24 V, the relay will
be enabled according to the time set at P283 (RL2) or P285 (RL3).
When the transition from 24 V to 0 V occurs, the programmed relay will
be disabled according to the time set at P284 (RL2) or P286 (RL3).
After the DIx transition, to enable or disable the programmed relay, it is
required that the DIx remains in on/off status during the time set at
parameters P283/P285 and P284/P286. Otherwise the relay will be reset.
Refer to figure 6.34.
Note:
For this function, program P279 and/or P280 = 28 (Timer).
P284
0.0 to 300
Time for RL2 OFF
[ 0.0 ]
0.1 s
P286
0.0 to 300
Time for RL3 OFF
[ 0.0 ]
0.1 s
Ix
= P290 (Current Ix) - User selected current reference point.
Is
= P003 (Motor Current).
Torque
= P009 (Motor Torque).
Tx
= P293 (Torque Tx) - User selected torque reference point.
Vpx
= P533 (Process Variable x) - User selected reference point.
Vpy
= P534 (Process Variable y) - User selected reference point.
Nt
= Total Reference (Refer to figure 6.26) after all scalings, offsets,
additions, etc.
Hx
= P294 (Hours Hx).
PLC
= Refer to PLC board manual.
Fx
= P370 (Frequency Fx) – Frequency reference defined by the user.