252
CHAPTER 8 - CFW-09 OPTIONS AND ACCESSORIES
ATTENTION!
The isolation of the analog input AI3 and the analog outputs AO1
I
and AO2
I
is
designed only to interrupt the ground loops. Do not connect these inputs to
high potentials.
ENCODER CONNECTION: Refer to item 8.2.
INSTALLATION
The EBB board is installed on the CC9 control board, secured with spacers
and connected via Terminal blocks XC11 (24 V) and XC3.
NOTE!
For the CFW-09 Size 1 Models (6 A, 7 A, 10 A and 13 A / 220-230 V and 3.6 A,
4 A, 5.5 A and 9 A / 380-480 V) the plastic cover must be removed to install the
EBB board.
Factory Default Function
Not Connected
Motor Thermistor Input 1 - PTC1
(P270 = 16 refer to figure 6.33). As DI
normal refer to P270 figure 6.34.
Motor Thermistor Input 2 - PTC2
(P270 = 16 refer to figure 6.33). As DI
normal refer to P270 figure 6.34.
0 V reference of the 24 Vdc source
Transistor Output 1: Not used
Commom point for Digital Input DI7
and Digital Outputs DO1 and DO2
Transistor Output 2: Not Used
Power Supply for the digital inputs/
outputs
Isolated digital input: Not Used
Reference for RS-485
RS-485 A-LINE (-)
RS-485 B-LINE (+)
Analog Input 3: Frequency Reference
Program
P221 = 3 or P222 = 3
0 V Reference for Analog Speed
Analog Output 1: Speed
0 V Reference for analog Output
Analog Output 2 : Motor Current
Avaliable to be connected to an external
power supply to energise the encoder
repeater output (XC8)
0 V reference of the external power supply
Terminal XC5
1
NC
2
DI8
3
DGND (DI8)
4
DGND
5
DO1
6
COMMOM
7
DO2
8
24 Vdc
9
DI7
10
SREF
11
A-LINE
12
B-LINE
13
AI3 +
14
AI3 -
15
AGND
I
16
AO1
I
17
AGND
I
18
AO2
I
19
+ V
20
COM 1
Specifications
Actuation: 3.9 k
Release:1.6 k
Min: resistance: 100
Referenced to DGND* through a 249
resistor
Grounded via a 249
resistor
Isolated, open collector, 24 Vdc, 50 mA
Max. required board (RL)
500
Isolated, open collector, 24 Vdc, 50 mA
Max. required board (RL)
500
24 Vdc ± 8 %. Isolated,
Capacity: 90 mA
Min. high level: 18 Vdc
Max. low level: 3 Vdc
Max. Voltage: 30 Vdc
Input Current.: 11 mA @ 24 Vdc
Isolated RS-485 serial port
Isolated analog input programmable on
P243:
(0 to 10) V or (0 to 20) mA/(4 to
20) mA
lin.: 10 bits (0.1 % of full scale
range) Impedance: 400 k
(0 to 10) V
500
[(0 to 20) mA/(4 to 20) mA]
Isolated analog Outputs signals:
(0 to 20) mA / (4 to 20) mA
Scales: refer to P251 and P253
lin.: 11 bits (0.5 % of full scale range)
Required board (RL)
600
External power supply: 5 V to 15 V,
consumption: 100 mA @ 5 V
Outputs not included.
PTC
500
RL
500
RL
Figure 8.4
- XC5 terminal block description (complete EBB board)
rpm
A