269
CHAPTER 8 - CFW-09 OPTIONS AND ACCESSORIES
Table 8.12
- Recommended braking resistor
Maximum
Braking
Current [A]
(1)
10
15
20
26
38
45
95
120
180
6
8
16
24
34
48
78
120
180
250
6
8
16
24
34
48
78
120
180
250
8.33
10
12.2
14.71
14.71
66.67
100
121.95
Rated
Current [A]
6
7 and 10
13 and 16
24
28
45
54
70 and 86
105 and 130
3.6 and 4
5.5
9 and 13
16
24
30
38 and 45
60 and 70
86 and 105
142
3.6 and 4
5.5
9 and 13
16
24
30
38 and 45
60 and 70
86 and 105
142
2.9 and 4.2
7
10
12
14
22, 27 and 32
44 and 53
63 and 79
CFW-09 Model
RMS Braking
Current [A]
(2)
5
7
10
13
18
22
48
60
90
3.5
4
10
14
21
27
39
60
90
125
3.5
4
10
14
21
27
39
60
90
125
4.2
5
6.1
7.4
7.4
33.33
50
61
Power Wiring
(BR, -UD, +UD)
mm² - AWG
2.5 - 14
2.5 - 14
4.0 - 12
6.0 - 10
10 - 8
10 - 8
35 - 3
50 - 1
95 - 3/0
2.5 - 14
2.5 - 14
4.0 - 12
6.0 - 10
10 - 8
10 - 8
25 - 4
50 - 1
95 - 3/0
120 - 4/0
2.5 - 14
2.5 - 14
4.0 - 12
6.0 - 10
10 - 8
10 - 8
25 - 4
50 - 1
95 - 3/0
120 - 4/0
2.5 - 14
2.5 - 14
2.5 - 14
4.0 - 12
2.5 - 14
95 - 3/0
95 - 3/0
95 - 3/0
Power Supply
Voltage [V]
220-230
380
and
400-415
440-460
and
480
500-525
and
575-600
Minimum
recommended
resistor
[ohms]
39
27
22
15
10
8.6
4.7
3.3
2.2
100
86
39
27
18
15
8.6
5.6
3.9
2.7
120
100
47
33
22
18
10
6.8
4.7
3.3
120
100
82
68
68
15
10
8.2
P
max
[kW]
(3)
3.9
6.1
8.8
10.1
14.4
17.4
42.4
47.5
71.3
3.6
5.5
10.0
15.6
20.8
34.6
52.3
80.6
126.4
168.8
4.3
6.4
12.0
19.0
25.4
41.5
60.8
97.9
152.3
206.3
12
10
12.81
20.83
15.3
337.5
225
184.5
P
rated
[kW]
(3)
0.97
1.3
2.2
2.5
3.2
4.2
10.8
11.9
17.8
1.2
1.4
3.9
5.3
7.9
10.9
13.1
20.1
31.6
42.2
1.5
1.6
4.7
6.5
9.7
13.1
15.2
24.5
38.1
51.6
2.08
2.5
3.05
3.68
3.68
16.67
25
30.49
The braking resistor is defined according to the deceleration time, load inertia
and resistive torque. In most cases a resistor with an ohmic value indicated on
table 8.12 and a power rating of 20 % of the driven motor can be used.
Use Wire type resistors with suitable insulation to withstand the instantaneous
current peaks.
For critical applications with very short braking times, high inertia loads (Ex:
centrifuges) or with very short and frequent duty cycles, contact WEG, to define
the most suitable resistor.