CFW-09 -
QUICK PARAMETER REFERENCE
28
Parameters
Function
Adjustable Range
Factory
Unit
User's
Page
Setting
Setting
6 = Modbus-RTU, 19200 bps,
even parity
7 = Modbus-RTU, 38400 bps,
no parity
8 = Modbus-RTU, 38400 bps,
odd parity
9 = Modbus-RTU, 38400 bps,
even parity
P313
(1)
Type of disabling by E28/E29/E30
0 = Disable via Start/Stop
0 = Disable via Start/Stop
-
199
1 = Disable via General
Enable
2 = Not Used
3 = Changes to LOCAL 1
4 = Changes to LOCAL 2
5 = Causes Fatal Error
P314
(1)
Time for Serial Watchdog
0.0 = Disable
0.0 = Disabled
s
200
Action
0.1 to 999.0 = Enable
P318
Watchdog detection for the
0 = Off
0 = Off
200
PLC board
1 = On
Flying Start/Ride-Through
P320
(1)
Flying Start/Ride-Through
0 = Inactive
0 = Inactive
-
200
1 = Flying Start
2 = Flying Start/Ride-Through
3 = Ride-Through
P321
(6)
Ud Line Loss Level
178 to 282 (P296 = 0)
252
V
200
307 to 487 (P296 = 1)
436
324 to 513 (P296 = 2)
459
356 to 564 (P296 = 3)
505
388 to 615 (P296 = 4)
550
425 to 674 (P296 = 5)
602
466 to 737 (P296 = 6)
660
486 to 770 (P296 = 7)
689
559 to 885 (P296 = 8)
792
P322
(6)
Ud Ride-Through
178 to 282 (P296 = 0)
245
V
201
307 to 487 (P296 = 1)
423
324 to 513 (P296 = 2)
446
356 to 564 (P296 = 3)
490
388 to 615 (P296 = 4)
535
425 to 674 (P296 = 5)
588
466 to 737 (P296 = 6)
644
486 to 770 (P296 = 7)
672
559 to 885 (P296 = 8)
773
P323
(6)
Ud Line Recover Level
178 to 282 (P296 = 0)
267
V
202
307 to 487 (P296 = 1)
461
324 to 513 (P296 = 2)
486
356 to 564 (P296 = 3)
534
388 to 615 (P296 = 4)
583
425 to 674 (P296 = 5)
638
466 to 737 (P296 = 6)
699
486 to 770 (P296 = 7)
729