CHAPTER 8 - CFW-09 OPTIONS AND ACCESSORIES
Figure 8.23
- Identification label
8.10.3.2 Mechanical Installation
The environmental operating conditions of the DBW are the same as of the
CFW-09 inverter (refer to item 3.1.1).
For panel installation, provide an additional airflow of 120 CFM (57 L/s) for
cooling of the braking module.
When installing module, provide free spaces around the module, as shown in
figure 8.24, where A = 100 mm (4 in), B = 40 mm (1.57 in) and C = 130 mm (5.12
in).
8.10.3.1
DBW-01 and DBW-02
Identification Label
Front View
A - View
A
Figure 8.24
- Free spaces for cooling
Rated Output
Data
DBW Type
Serial Number
WEG Item N
o