71
CHAPTER 3 - INSTALLATION AND CONNECTION
The following tables 3.12 and 3.13 show the Schaffner filters list for CFW-09
inverter series with 380-480 V and 220-230 V power supply, respectively.
3.3.3 Schaffner Filters
Figure 3.19
- Schaffner EMC filters connection in CFW-09 frequency inverters
Controling and Signal Wiring
Output CM
Choke
Transformer
Ground Rod/Grid or
Building Steel
Structure
Panel or Metallic Enclosure
Protective Grounding - PE
Motor
PE
CFW - 09
U
W
V
L2
L1
L3
E
F1
F2
F3
PE
Filter
Q1
XC1 1 to 28
F
ilt
e
r
In
p
u
t
F
ilt
e
r
O
u
tp
u
t
E
L3
L2
L1
PE
XR
T
S
Input CM Choke
FN-3258-7-45
FN-3258-7-45
FN-3258-16-45
FN-3258-16-45
FN-3258-30-47
FN-3258-55-52
FN-3258-55-52
FN-3258-100-35
3.6 A
4 A, 5 A
9 A
13 A
16 A
24 A
30 A
30 A
38 A
45 A
RS-232
EBA RS-485
Serial Interface
EBA RS-485
Serial Interface
No
No
EBB
RS-485 Serial
Interface
No
No
Model
Optional Device
Input
filter
Input
CM
Choke
Output
CM
Choke
No
No
No
No
No
No
No
No
No
No
No
No
No
Yes
No
No
Inside
Metallic
Panel
Electromagnetic radiation
disturbance level
(Product Standard
EN61800-3 (1996)
+ A11 (2000)
(1)
Conducted
Emission
Class
(2)
B
B
B
B
B
A 1
A 1
A 1
380-480 V power supply:
First environment, restricted
distribution
Second environment,
unrestricted distribution
Second environment,
unrestricted distribution
First environment, restricted
distribution
First environment, restricted
distribution
First environment, restricted
distribution
First environment, restricted
distribution
First environment, restricted
distribution
No
No
No
No
No
Schaffner 203 (1151-
042) -
2 turns (filter input
side)
No
2 x Schaffner 203
(1151-042) - (filter
input/output
sides)
Table 3.12
- Schaffner filters list for CFW-09 inverter series with 380-480 V power supply