Programming Basic Instructions
5-12
5
5.7 INCOMPATIBILITY BETWEEN PARAMETERS
If any of the combinations listed below occur, the CFW-11 goes to the "Config" state.
1) Two or more DIx (P0263...P0270) programmed for (4 = FWD Run).
2) Two or more DIx (P0263...P0270) programmed for (5 = REV Run).
3) Two or more DIx (P0263...P0270) programmed for (6 = 3-Wire Start).
4) Two or more DIx (P0263...P0270) programmed for (7 = 3-Wire Stop).
5) Two or more DIx (P0263...P0270) programmed for (8 = FWD/REV).
6) Two or more DIx (P0263...P0270) programmed for (9 = LOC/REM).
7) Two or more DIx (P0263...P0270) programmed for (11 = Increase E.P.).
8) Two or more DIx (P0263...P0270) programmed for (12 = Decrease E.P.).
9) Two or more DIx (P0263...P0270) programmed for (14 = Ramp 2).
10) Two or more DIx (P0263...P0270) programmed for (15 = Speed/Torque).
11) Two or more DIx (P0263...P0270) programmed for (22 = Manual/Automatic).
12) Two or more DIx (P0263...P0270) programmed for (24 = Disable Flying Start).
13) Two or more DIx (P0263...P0270) programmed for (25 = DC Link Regulator).
14) Two or more DIx (P0263...P0270) programmed for (26 = Programming Off).
15) Two or more DIx (P0263...P0270) programmed for (27 = Load User 1/2).
16) Two or more DIx (P0263...P0270) programmed for (28 = Load User 3).
17) Two or more DIx (P0263...P0270) programmed for (29 = DO2 Timer).
18) Two or more DIx (P0263...P0270) programmed for (30 = DO3 Timer).
19) DIx (P0263...P0270) programmed for (4 = FWD Run) without DIx (P0263...P0270) programmed for
(5 = REV Run).
20) DIx (P0263...P0270) programmed for (5 = REV Run) without DIx (P0263...P0270) programmed for
(4 = FWD Run).
21) DIx (P0263...P0270) programmed for (6 = 3-Wire Start) without DIx (P0263...P0270) programmed for
(7 = 3-Wire Stop).
22) DIx (P0263...P0270) programmed for (7 = 3-Wire Stop) without DIx (P0263...P0270) programmed for
(6 = 3-Wire Start).
23) P0221 or P0222 programmed for (8 = Multispeed) without DIx (P0266...P0268) programmed for
(13 = Multispeed).
24) P0221 or P0222 not programmed for (8 = Multispeed) with DIx (P0266...P0268) programmed for
(13 = Multispeed).
Summary of Contents for CFW-11 Series
Page 2: ......
Page 54: ...2 4 2 General Information ...
Page 58: ...About the CFW 11 3 3 4 ...
Page 74: ...Inverter Model and Accessories Identification 5 14 6 ...
Page 86: ...Inverter Model and Accessories Identification 6 12 6 ...
Page 94: ...Available Control Types 8 2 8 ...
Page 118: ...VVW Control 10 8 10 ...
Page 182: ...Functions Common to All the Control Modes 12 26 12 ...
Page 220: ...Dynamic Braking 14 4 14 ...