Vector Control
11-16
11
When, on the data sheet, it is considered connection in YY or ∆∆ and the motor is connected in ∆:
P409 =
4
x R
s
3
P411 =
4
x
σ
ls
3
When, on the data sheet, it is considered connection in ∆ and the motor is connected in YY:
P409 =
R
s
4
P411 =
σ
ls
4
When, on the data sheet, it is considered connection in ∆ and the motor is connected in ∆∆:
P409 =
R
s
12
P411 =
σ
ls
12
When, on the data sheet, it is considered connection in ∆ and the motor is connected in ∆:
P409 =
R
s
3
P411 =
σ
ls
3
Regardless of the connection type used on the motor and of the connection type indicated on the data sheet,
parameters P410 and P412 are defined as:
P410=I
m
P412= T
r
For conditions not included above, contact WEG.
11.8 VECTOR CONTROL [29]
11.8.1 Speed Regulator [90]
The parameters related to the CFW-11 speed regulator are presented in this group.
P0160 – Speed Regulator Configuration
Adjustable
Range:
0 = Normal
1 = Saturated
Factory
Setting:
0
Properties:
CFG, PM and Vector
Access groups
via HMI:
01 PARAMETER GROUPS
29 Vector Control
90 Speed Regulator
Description:
Adjust P0160 = 1 in applications where stable torque is desired, as in a material winding process; in those cases,
the speed reference is always maintained greater than the speed feedback value, aiming at saturating the speed
regulator, that is, keeping its output equal to the value adjusted in P0169 or P0170 during the process.
If it is used for speed control F022 may occur, even if the DC link voltage regulation is active (P0185 < default value).
Summary of Contents for CFW-11 Series
Page 2: ......
Page 54: ...2 4 2 General Information ...
Page 58: ...About the CFW 11 3 3 4 ...
Page 74: ...Inverter Model and Accessories Identification 5 14 6 ...
Page 86: ...Inverter Model and Accessories Identification 6 12 6 ...
Page 94: ...Available Control Types 8 2 8 ...
Page 118: ...VVW Control 10 8 10 ...
Page 182: ...Functions Common to All the Control Modes 12 26 12 ...
Page 220: ...Dynamic Braking 14 4 14 ...