11-23
11
Vector Control
P0183 – Current in the I/f Mode
Adjustable
Range:
0 to 9
Factory
Setting:
1
Properties:
Sless
Access groups
via HMI:
01 PARAMETER GROUPS
29 Vector Control
93 I/F Control
Description:
It defines the current to be applied to the motor when the inverter is operating in the I/f mode, i.e., with the motor
speed below the value defined by P0182.
Table 11.5 -
Current applied in the I/f mode
P0183
Current in the I/f mode as a percentage of P0410 (I
m
)
0
100 %
1
120 %
2
140 %
3
160 %
4
180 %
5
200 %
6
220 %
7
240 %
8
260 %
9
280 %
11.8.5 Self-Tuning [05] and [94]
In that group are the parameters that are related to the motor and can be estimated by the inverter during the
self-tuning routine.
P0408 – Run Self-Tuning
Adjustable
Range:
0 = No
1 = No Rotation
2 = Run for I
m
3 = Run for T
m
4 = Estimate T
m
Factory
Setting:
0
Properties:
CFG, Vector and VVW
Access groups
via HMI:
01 PARAMETER GROUPS
05 SELF-TUNING
29 Vector Control
or
94 Self-tuning
NOTE!
The commands via communication network, SoftPLC and PLC11 remain inactive during the self-tuning.
Summary of Contents for CFW-11 Series
Page 2: ......
Page 54: ...2 4 2 General Information ...
Page 58: ...About the CFW 11 3 3 4 ...
Page 74: ...Inverter Model and Accessories Identification 5 14 6 ...
Page 86: ...Inverter Model and Accessories Identification 6 12 6 ...
Page 94: ...Available Control Types 8 2 8 ...
Page 118: ...VVW Control 10 8 10 ...
Page 182: ...Functions Common to All the Control Modes 12 26 12 ...
Page 220: ...Dynamic Braking 14 4 14 ...