3-40 | CFW-11M RB
Installation and Connection
Do not ground
Converter
side
Isolate with tape
Figure 3.54 -
Shield connection
5. Relays, contactors, solenoids or coils of electromechanical brakes installed close to the converter may
eventually create interferences in the control circuit. To eliminate this effect, RC suppressors (with AC
power supply) or free-wheel diodes (with DC power supply) shall be connected in parallel to the coils of
these devices.
Example of connection of control cable shield
Figure 3.55 -
Example of shield connection for the control wiring and synchronism
3.4.10 Typical Control Connection
Control connection 1 - Control via Keypad (HMI) with General Enable function.
The factory default settings allows the converter to operate in local mode. This operation mode is
recommended for first-time users due to its easiness of implementation.
For the start-up in this operation mode, please follow instructions listed in chapter 5.
DI1 is already set to General Enable as factory default (P0263 = 2).