Digital and Analog Inputs and Outputs
12-18 | CFW500
12
a) RUN/STOP
It enables or disables the motor rotation through the acceleration and deceleration ramp.
Acceleration ramp
Deceleration
ramp
Time
Time
Active
Inactive
DIx
Output
frequency
Figure 12.6:
Example of the Run/Stop function
b) GENERAL ENABLE
It enables the motor rotation through the acceleration ramp and disables it by cutting off the pulses immediately;
the motor stops by inertia.
Acceleration ramp
Motor runs free
Time
Time
Active
Inactive
DIx
Output
frequency
Figure 12.7:
Example of the General Enable function
c) QUICK STOP
When inactive, it disables the inverter by the 3
rd
Ramp by P0106.
P0106 -
Deceleration ramp
Time
Time
Active
Inactive
DIx - Quick Stop
Output
frequency
Figure 12.8:
Example of the Quick Stop function