Digital and Analog Inputs and Outputs
CFW500 | 12-21
12
DIx - Run/Stop
DIx - Decelerate
DIx - Decelerate
Time
Time
Reset
P0133
&
Reference
Time
Inactive
Inactive
Active
Active
Output
frequency
Ramp
Enabling (RUN)
Time
Active
Inactive
DIx - Accelerate
DIx - Accelerate
Figure 12.13:
Example of the Electronic Potentiometer (E.P.) function
j) MULTISPEED
The Multispeed reference, as described in
Item 7.2.3 Speed Reference Parameters on page 7-9
, allows selecting
one among eight reference levels pre-defined in parameters P0124 to P0131 by the combination of up to three
digital inputs. For further details, refer to
Chapter 7 LOGICAL COMMAND AND SPEED REFERENCE on page 7-1
k) 2
nd
RAMP
If DIx is inactive, the inverter uses the default ramp by P0100 and P0101; otherwise, it will use the 2
nd
Ramp by
P0102 and P0103.
DIx - Run/Stop
DIx - 2
nd
Ramp
Time
P0103
P0102
P0101
P0100
Time
Inactive
Active
Output
frequency
Time
Active
Inactive
Figure 12.14:
Example of the 2
nd
Ramp function
l) NO EXTERNAL ALARM
If DIx is inactive, the inverter will activate the external alarm A0090.
Summary of Contents for CFW500 V1.8X
Page 2: ......
Page 4: ......
Page 8: ...Contents...
Page 34: ...General Information 2 4 CFW500...
Page 38: ...About the CFW500 3 4 CFW500 3...
Page 42: ...HMI and Basic Programming 4 4 CFW500 4...
Page 52: ...Programming Basic Instructions 5 10 CFW500 5...
Page 56: ...Identification of the Inverter Model and Accessories 6 4 CFW500 6...
Page 76: ...Available Motor Control Types 8 4 CFW500 8...
Page 84: ...V f Scalar Control 9 8 CFW500 9...
Page 170: ...Communication 17 8 CFW500 17...