Digital and Analog Inputs and Outputs
12-24 | CFW500
12
Description:
By using this parameter, it is possible to view the CFW500 digital output status.
The value of P0013 is indicated in hexadecimal, where each bit indicates the status of a digital output, that is,
if the Bit
0
is “0”, DO1 is inactive; if the Bit
0
is “1”, DO1 is active, and so on up to DO5. Therefore, DOx active (1)
means closed transistor or relay, inactive (0) means open transistor or relay.
NOTE!
Parameter P0013 requires the user to know the conversion between binary and hexadecimal
numerical system.
P0275 – DO1 Output Function
P0276 – DO2 Output Function
P0277 – DO3 Output Function
P0278 – DO4 Output Function
P0279 – DO5 Output Function
Adjustable
Range:
0 to 44
Factory
Setting:
P0275 = 13
P0276 = 2
P0277 = 0
P0278 = 0
P0279 = 0
Properties:
Access Groups
via HMI:
I/O
Description:
These parameters define the DOx digital output function, as per