Reading Parameters
CFW500 | 16-1
16
16 READING PARAMETERS
In order to simplify the view of the main inverter reading variables, you may directly access the READ – “Reading
Parameters” menu of the CFW500 HMI.
It is important to point out that all the parameters of this group can only be viewed on the HMI display, and cannot
be changed by the user.
P0001 – Speed Reference
Adjustable
Range:
0 to 65535
Factory
Setting:
Properties:
ro
Access Groups
via HMI:
READ
Description:
This parameter presents, regardless the origin source, the speed reference value in the unit and scale defined for
the reference by P0208, P0209 and P0212. The full scale and reference unit in the factory default are 66.0 Hz for
P0204 = 5 and 55.0 Hz for P0204 = 6.
P0002 – Output Speed (Motor)
Adjustable
Range:
0 to 65535
Factory
Setting:
Properties:
ro
Access Groups
via HMI:
READ
Description:
Parameter P0002 indicates the speed imposed to the inverter output at the same scale defined for P0001. In
this parameter, the compensations made to the output frequency are not shown. To read the compensated
output, use P0005.
P0003 – Motor Current
Adjustable
Range:
0.0 to 200.0 A
Factory
Setting:
Properties:
ro
Access Groups
via HMI:
READ
Description:
It indicates the inverter output current in amperes RMS (Arms).
P0004 – DC Link Voltage (Ud)
Adjustable
Range:
0 to 2000 V
Factory
Setting:
Properties:
ro
Access Groups
via HMI:
READ
Summary of Contents for CFW500 V1.8X
Page 2: ......
Page 4: ......
Page 8: ...Contents...
Page 34: ...General Information 2 4 CFW500...
Page 38: ...About the CFW500 3 4 CFW500 3...
Page 42: ...HMI and Basic Programming 4 4 CFW500 4...
Page 52: ...Programming Basic Instructions 5 10 CFW500 5...
Page 56: ...Identification of the Inverter Model and Accessories 6 4 CFW500 6...
Page 76: ...Available Motor Control Types 8 4 CFW500 8...
Page 84: ...V f Scalar Control 9 8 CFW500 9...
Page 170: ...Communication 17 8 CFW500 17...