Reading Parameters
16-4 | CFW500
16
P0009 – Motor Torque
Adjustable
Range:
-1000.0 to 1000.0 %
Factory
Setting:
Properties:
ro, V VW
Access Groups
via HMI:
READ
Description:
It indicates the torque developed by the motor in relation to the rated torque.
P0010 – Output Power
Adjustable
Range:
0.0 to 6553.5 kW
Factory
Setting:
Properties:
ro
Access Groups
via HMI:
READ
Description:
It indicates the electric power in the inverter output. This power is determined through the formula:
P0010 = 1.732 x P0003 x P0007 x P0011.
Where: 1.732 = √3 .
P0003 is the output current measured.
P0007 is the reference output voltage (or estimated).
P0011 is the value of the cosine [(vector angle of the reference output voltage) – (vector angle of the output
current measured)].
P0011 – Power Factor
Adjustable
Range:
-1.00 to 1.00
Factory
Setting:
Properties:
ro
Access Groups
via HMI:
READ
Description:
It indicates the power factor, that is, the relationship between the real power and the total power absorbed by
the motor.
P0012 – Digital Input Status
Refer to
Section 12.5 DIGITAL INPUTS on page 12-14
P0013 – Digital Output Status
Refer to
Summary of Contents for CFW500 V1.8X
Page 2: ......
Page 4: ......
Page 8: ...Contents...
Page 34: ...General Information 2 4 CFW500...
Page 38: ...About the CFW500 3 4 CFW500 3...
Page 42: ...HMI and Basic Programming 4 4 CFW500 4...
Page 52: ...Programming Basic Instructions 5 10 CFW500 5...
Page 56: ...Identification of the Inverter Model and Accessories 6 4 CFW500 6...
Page 76: ...Available Motor Control Types 8 4 CFW500 8...
Page 84: ...V f Scalar Control 9 8 CFW500 9...
Page 170: ...Communication 17 8 CFW500 17...