0
Quick Reference of Parameters, Alarms and Faults
0-10 | CFW500
Parameter
Description
Adjustable
Range
Factory
Setting
User
Setting Properties
Groups
Page
P0304
Skip Frequency 2
0.0 to 500.0 Hz
30.0 Hz
P0306
Skip Band
0.0 to 25.0 Hz
0.0 Hz
P0308
Serial Address
1 to 247
1
NET
P0310
Serial Baud Rate
0 = 9600 bits/s
1 = 19200 bits/s
2 = 38400 bits/s
1
NET
P0311
Serial Bytes Config.
0 = 8 bits, no, 1
1 = 8 bits, even, 1
2 = 8 bits, odd, 1
3 = 8 bits, no, 2
4 = 8 bits, even, 2
5 = 8 bits, odd, 2
1
NET
P0312
Serial Protocol (1) (2)
0 = HMIR (1)
1 = Reserved
2 = Modbus RTU (1)
3 = Reserved
4 = Reserved
5 = Master RTU (1)
6 = HMIR (1) + Modbus RTU
(2)
7 = Modbus RTU (2)
8 to 11 = Reserved
12 = HMI (1)/RTU Master (2)
13 = RTU Master (2)
2
cfg
NET
P0313
Communic. Error Action
0 = Inactive
1 = Ramp Stop
2 = General Disable
3 = Go to LOC
4 = LOC Keep Enab
5 = Cause Fault
1
NET
P0314
Serial Watchdog
0.0 to 999.0 s
0.0 s
NET
P0316
Serial Interf. Status
0 = Inactive
1 = Active
2 = Watchdog Error
ro
READ,
NET
P0320
Flying Start/Ride-Through
0 = Inactive
1 = Flying Start (FS)
2 = FS / RT
3 = Ride-Through (RT)
0
cfg
P0331
Voltage Ramp
0.2 to 60.0 s
2.0 s
P0340
Auto-Reset Time
0 to 255 s
0 s
P0343
Fault/Alarm Mask
Bit 0 = F0074
Bit 1 = F0048
Bit 2 = F0078
Bit 3 = F0079
Bit 4 = F0076
Bit 5 = F0179
Bit 6 to 15 = Reserved
0007h
cfg
P0349
Ixt Alarm Level
70 to 100 %
85 %
cfg
P0397
Control Configuration
Bit 0 = Regen. Slip Comp.
Bit 1 = Dead Time Comp.
Bit 2 = Is Stabilization
Bit 3 = Red. P0297 in A0050
000Bh
cfg
P0399
Motor Rated Efficiency
50.0 to 99.9 %
75.0 %
cfg, V V W
MOTOR,
STARTUP
P0400
Motor Rated Voltage
200 to 600 V
According to
cfg, V V W
MOTOR,
STARTUP
P0401
Motor Rated Current
0.0 to 200.0 A
1.0xI
nom
cfg
MOTOR,
STARTUP
P0402
Motor Rated Speed
0 to 30000 rpm
1710 (1425) rpm
cfg
MOTOR,
STARTUP
P0403
Motor Rated Frequency
0 to 500 Hz
60 (50) Hz
cfg
MOTOR,
STARTUP
Summary of Contents for CFW500 V1.8X
Page 2: ......
Page 4: ......
Page 8: ...Contents...
Page 34: ...General Information 2 4 CFW500...
Page 38: ...About the CFW500 3 4 CFW500 3...
Page 42: ...HMI and Basic Programming 4 4 CFW500 4...
Page 52: ...Programming Basic Instructions 5 10 CFW500 5...
Page 56: ...Identification of the Inverter Model and Accessories 6 4 CFW500 6...
Page 76: ...Available Motor Control Types 8 4 CFW500 8...
Page 84: ...V f Scalar Control 9 8 CFW500 9...
Page 170: ...Communication 17 8 CFW500 17...