P0220 – Local/Remote Selection
Adjustable
Range:
0 = Always Local
1 = Always Remote
2 = Local/Remote HMI Key (LOC)
3 = Local/Remote HMI Key (REM)
4 = Digital Input (DIx)
5 = Serial/USB (LOC)
6 = Serial/USB (REM)
7 = Not Used
8 = Not Used
9 = CO/DN/PB/Eth (LOC)
10 = CO/DN/PB/Eth (REM)
11 = SoftPLC
Factory
Setting:
2
Properties:
cfg
Access Groups
via HMI:
I/O
Description:
It defines the command origin source which will select between Local situation and Remote situation, where:
LOC: means Local situation default.
REM: means Remote situation default.
DIx: according to function programmed for digital input in P0263 to P0270.
CO/DN/PB/Eth
: CANopen, DeviceNet, Profibus DP or Ethernet Interface.
P0221 – Speed Reference Selection – LOCAL Situation
P0222 – Speed Reference Selection – REMOTE Situation
Adjustable
Range:
0 = HMI Keys
1 = AI1
2 = AI2
3 = AI3
4 = Frequency input (FI)
5 = AI1 + AI2 > 0 (Sum AIs > 0)
6 = AI1 + AI2 (Sum AIs)
7 = E.P.
8 = Multispeed
9 = Serial/USB
10 = Not Used
11 = CO/DN/PB/Eth
12 = SoftPLC
13 = Not Used
14 = AI1 > 0
15 = AI2 > 0
16 = AI3 > 0
17 = FI > 0
Factory
Setting:
P0221 = 0
P0222 = 1
Properties:
cfg
Access Groups
via HMI:
I/O
Summary of Contents for CFW500 V1.8X
Page 2: ......
Page 4: ......
Page 8: ...Contents...
Page 34: ...General Information 2 4 CFW500...
Page 38: ...About the CFW500 3 4 CFW500 3...
Page 42: ...HMI and Basic Programming 4 4 CFW500 4...
Page 52: ...Programming Basic Instructions 5 10 CFW500 5...
Page 56: ...Identification of the Inverter Model and Accessories 6 4 CFW500 6...
Page 76: ...Available Motor Control Types 8 4 CFW500 8...
Page 84: ...V f Scalar Control 9 8 CFW500 9...
Page 170: ...Communication 17 8 CFW500 17...