Digital and Analog Inputs and Outputs
12-26 | CFW500
12
P0290 – Ix Current
Adjustable
Range:
0.0 to 200.0 A
Factory
Setting:
1.0xI
nom
Properties:
Access Groups
via HMI:
I/O
Description:
Current level to activate the relay output in the Is>Ix (6) and Is<Ix (7) functions. The actuation occurs on a
hysteresis with upper level in P0290 and lower by: P0290 - 0.05xP0295, that is, the equivalent value is Amperes
for 5 % of P0295 below P0290.
P0293 – Tx Torque
Adjustable
Range:
0 to 200 %
Factory
Setting:
100 %
Properties:
Access Groups
via HMI:
I/O
Description:
Torque percentage level to activate the relay output in the Torque > Tx (8) and Torque < Tx (9) functions. The
actuation occurs on a hysteresis with upper level in P0293 and lower by: P0293 - 5 %. This percentage value
is related to the motor rated torque matched to the inverter power.