Logical Command and Speed Reference
CFW500 | 7-7
7
P0224 – Run / Stop Selection – LOCAL Situation
P0227 – Run / Stop Selection – REMOTE Situation
Adjustable
Range:
0 = HMI Keys
1 = DIx
2 = Serial/USB
3 = Not Used
4 = CO/DN/PB/Eth
5 = SoftPLC
Factory
Setting:
P0224 = 0
P0227 = 1
Properties:
cfg
Access Groups
via HMI:
I/O
Description:
These parameters define the origin source for the “Run/Stop" command in the Local and Remote situation. This
command corresponds to the functions implemented in any of the command sources able to enable the motor
movement, that is, General Enable, Ramp Enable, Forward Run, Reverse Run, Turn ON, Turn OFF, JOG, etc.
P0225 – JOG Selection – LOCAL Situation
P0228 – JOG Selection – REMOTE Situation
Adjustable
Range:
0 = Disable
1 = HMI Keys
2 = DIx
3 = Serial/USB
4 = Not Used
5 = CO/DN/PB/Eth
6 = SoftPLC
Factory
Setting:
P0225 = 1
P0228 = 2
Properties:
cfg
Access Groups
via HMI:
I/O
Description:
These parameters define the origin source for the JOG function in the Local and Remote situation. The
JOG function means a Run/Stop command added to the reference defined by P0122; see
Reference Parameters on page 7-9
.
7.2 SPEED REFERENCE
The speed reference is the value applied to the input of the acceleration ramp module (P0001) to control the
frequency applied to the inverter output (P0002) and consequently the motor shaft speed.
Inside the CPU, the inverter uses signed 16 bit variables to treat the speed references. Besides, the full scale of
the reference, output frequency and related variables are defined in 500.0 Hz. On the other hand, depending
on the source, this scale is conveniently modified considering the interface with the user by standardization or
application requirements.
In general, the digital references are defined by parameters like: HMI keys (P0121), Multispeed (P0124 to P0131),
E.P. and JOG have a scale from 0.0 to 500.0 Hz with resolution of 0.1 Hz. On the other hand the speed reference
via analog input uses a 16-bit internal scale with signal with the full scale in 500.0 Hz.
The speed reference via HMI can be the JOG key or electronic potentiometer of the keys "
" and "
" on
parameter P0121.
Summary of Contents for CFW500 V1.8X
Page 2: ......
Page 4: ......
Page 8: ...Contents...
Page 34: ...General Information 2 4 CFW500...
Page 38: ...About the CFW500 3 4 CFW500 3...
Page 42: ...HMI and Basic Programming 4 4 CFW500 4...
Page 52: ...Programming Basic Instructions 5 10 CFW500 5...
Page 56: ...Identification of the Inverter Model and Accessories 6 4 CFW500 6...
Page 76: ...Available Motor Control Types 8 4 CFW500 8...
Page 84: ...V f Scalar Control 9 8 CFW500 9...
Page 170: ...Communication 17 8 CFW500 17...