12
Functions Common to all the Control Modes
12-6 | CFW700
P0133 – Minimum Speed Reference Limit
Adjustable
Range:
0 to 18000 rpm
Factory
Setting:
90 rpm
(75 rpm)
P0134 – Maximum Speed Reference Limit
Adjustable
Range:
0 to 18000 rpm
Factory
Setting:
1800 pm
(1500 rpm)
Properties:
Access groups
via HMI:
BASIC
Description:
They define the maximum/minimum values for the motor speed reference when the inverter is enabled. They
are valid for any type of reference signal. For details on the actuation of P0133, refer to the parameter P0230
(Dead Zone of the Analog Inputs).
-10 V
Speed
Reference
Output Speed
Speed
Reference
P0134
P0133
-P0133
-P0134
+10 V
P0134
P0133
0
0 ......................100 %
0 ........................10 V
0 ..................... 20 mA
4 mA .................. 20 mA
10 V ............................0
20 mA ........................0
20 mA ...................4 mA
Output Speed
Figure 12.3:
Speed limits considering the “Dead Zone” active (P0230=1)