0
Quick Parameter Reference, Faults and Alarms
0-4 | CFW700
Param.
Description
Adjustable Range
Factory Setting
User
Setting
Propr.
Grorps
Pag.
P0200
Password
0 = Inactive
1 = Active
2 = Change Password
1 = Active
HMI
5-3
P0202
Control Type
0 = V/f 60 Hz
1 = V/f 50 Hz
2 = V/f Adjustable
3 = VVW
4 = Sensorless
5 = Encoder
0 = V/f 60 Hz
cfg
9-5
P0204
Load/Save Parameters
0 = Not Used
1 = Not Used
2 = Reset P0045
3 = Reset P0043
4 = Reset P0044
5 = Load 60 Hz
6 = Load 50 Hz
7 = Load User 1
8 = Load User 2
9 = Save User 1
10 = Save User 2
0 = Not Used
cfg
7-1
P0205
Main Display Parameter
Selection
0 to 1199
2
HMI
5-3
P0206
Secondary Display
Parameter Selection
0 to 1199
1
HMI
5-3
P0207
Bar Graph Parameter
Selection
0 to 1199
3
HMI
5-3
P0208
Main Display Scale Factor
0.1 to 1000.0 %
100.0 %
HMI
5-4
P0209
Engineering Unit
0 = None
1 = V
2 = A
3 = rpm
4 = s
5 = ms
6 = N
7 = m
8 = Nm
9 = mA
10 = %
11 = °C
12 = CV
13 = Hz
14 = HP
15 = h
16 = W
17 = kW
18 = kWh
19 = H
3 = rpm
HMI
5-4
P0210
Decimal Point 1
0 = wxyz
1 = wxy.z
2 = wx.yz
3 = w.xyz
0 = wxyz
HMI
5-4
P0211
Secondary Display Scale
Factor
0.1 to 1000.0 %
100.0 %
HMI
5-4
P0212
Decimal Point 2
0 = wxyz
1 = wxy.z
2 = wx.yz
3 = w.xyz
0 = wxyz
HMI
5-4
P0213
Bar Full Scale
1 to 65535
1
HMI
5-5
P0216
HMI Backlighting
0 to 15
15
HMI
5-5
P0217
Zero Speed Disable
0 = Inactive
1 = Active
0 = Inactive
cfg
12-7
P0218
Condition to Leave Zero
Speed Disable
0 = Reference or Speed
1 = Reference
0 = Reference or
Speed
12-7
P0219
Delay for Zero Speed
Disable
0 to 999 s
0 s
12-8
Summary of Contents for CFW700
Page 2: ......
Page 4: ......
Page 8: ...Summary...
Page 34: ...2 General Information 2 4 CFW700...
Page 38: ...3 About the CFW700 3 4 CFW700...
Page 56: ...7 Starting up and Settings 7 4 CFW700...
Page 58: ...8 Available Control Types 8 2 CFW700...
Page 78: ...10 VVW Control 10 8 CFW700...
Page 158: ...13 Digital and Analog Inputs and Outputs 13 28 CFW700...