13
Digital and Analog Inputs and Outputs
13-8 | CFW700
Table 13.3:
Full scale
Scale of the Analog Output Indications
Variable
Full Scale (*)
Speed Reference
P0134
Total Reference
Real Speed
Encoder Speed
Torque Current Reference
2.0 x I
nomHD
Torque Current
Torque Current > 0
Motor Torque
2.0 x I
nom
Output Current
1.5 x I
nomHD
Active Current
Output Power
1.5 x √3 x P0295 x P0296
Motor Ixt
100 %
SoftPLC
32767
P0696 Value
P0697 Value
(*)
When the signal is inverse (10 to 0 V, 20 to 0 mA or 20 to 4 mA) the values in the table
become the beginning of the scale.
P0253 – AO1 Signal Type
P0256 – AO2 Signal Type
Adjustable
Range:
0 = 0 to 10 V / 20 mA
1 = 4 to 20 mA
2 = 10 V / 20 mA to 0
3 = 20 to 4 mA
Factory
Setting:
0
Properties:
cfg
Access groups
via HMI:
I/O
Description:
These parameters configure if the analog output signal will be in current or voltage, with direct or inverse
reference.
In order to adjust these parameters, it is also necessary to set the “DIP switches” of the control board according
to the
and
Table 13.4:
DIP switches related to the analog outputs
Parameter
Output
Switch
Location
P0253
AO1
S1.3
Control Board
P0256
AO2
S1.4
Table 13.5:
Configuration of the analog outputs AO1 and AO2 signals
P0253, P0256
Output Signal
Switch Position
0
(0 to 10) V / (0 to 20) mA
On / Off
1
(4 to 20) mA
Off
2
(10 to 0) V / (20 to 0) mA
On / Off
3
(20 to 4) mA
Off
For AO1 and AO2, when current signals are used, the switch corresponding to the desired output must be set in
the “OFF” position.
Summary of Contents for CFW700
Page 2: ......
Page 4: ......
Page 8: ...Summary...
Page 34: ...2 General Information 2 4 CFW700...
Page 38: ...3 About the CFW700 3 4 CFW700...
Page 56: ...7 Starting up and Settings 7 4 CFW700...
Page 58: ...8 Available Control Types 8 2 CFW700...
Page 78: ...10 VVW Control 10 8 CFW700...
Page 158: ...13 Digital and Analog Inputs and Outputs 13 28 CFW700...