Digital and Analog Inputs and Outputs
13
CFW700 | 13-15
P0279 – DO5 Function
Adjustable
Range:
0 = Not Used
1 = N* > Nx
2 = N > Nx
3 = N < Ny
4 = N = N*
5 = Zero Speed
6 = Is > Ix
7 = Is < Ix
8 = Torque > Tx
9 = Torque < Tx
10 = Remote
11 = Run
12 = Ready
13 = No Fault
14 = No F070
15 = No F071
16 = No F006/21/22
17 = No F051
18 = No F072
19 = 4-20 mA OK
20 = P0695 Value
21 = Forward
22 = Ride-Through
23 = Pre-Charge OK
24 = Fault
25 = Enabled Time > Hx
26 = SoftPLC
27 = N>Nx/Nt>Nx
28 = F > Fx (1)
29 = F > Fx (2)
30 = STO
31 = No F160
32 = No Alarm
33 = No Fault and No Alarm
34 = Application Function 1
35 = Application Function 2
36 = Application Function 3
37 = Application Function 4
38 = Application Function 5
39 = Application Function 6
40 = Application Function 7
41 = Application Function 8
Factory
Setting:
P0275=13
P0276=2
P0277=1
P0278=0
P0279=0
Properties:
cfg
Access groups
via HMI:
I/O
Description:
They program the functions of the digital outputs, according to the options presented previously.
When the condition declared by the function is true, the digital output will be activated.
Example: Is>Ix function – when Is>Ix then DOx=saturated transistor and/or relay with the coil energized, and
when Is≤Ix then DOx=open transistor and/or relay with the coil not energized.
Summary of Contents for CFW700
Page 2: ......
Page 4: ......
Page 8: ...Summary...
Page 34: ...2 General Information 2 4 CFW700...
Page 38: ...3 About the CFW700 3 4 CFW700...
Page 56: ...7 Starting up and Settings 7 4 CFW700...
Page 58: ...8 Available Control Types 8 2 CFW700...
Page 78: ...10 VVW Control 10 8 CFW700...
Page 158: ...13 Digital and Analog Inputs and Outputs 13 28 CFW700...