English
TROUBLESHOOTING AND MAINTENANCE
Protection/Alarm
Description
Possible causes
A1304:
Slot C high temperature
Temperature in the accessory is high.
- Temperature around the inverter close to 60
◦
C.
F1305:
Slot C overtemperature
Accessory overtemperature.
- Temperature around the inverter above 60
◦
C.
A1306:
Slot C enc. A cable
disconnection
Encoder signal not detected correctly
Note:
It can be disabled by setting C5.n.6.2, where n is the
number of the slot where the accessory is installed.
- Broken or disconnected signal cable.
- Encoder connection error.
- Encoder without power supply.
F1307:
Slot C enc. A cable
disconnection
Encoder signal not detected correctly
Note:
It can be disabled by setting C5.n.6.2, where n is the
number of the slot where the accessory is installed.
- Broken or disconnected signal cable.
- Encoder connection error.
- Encoder without power supply.
A1308:
Slot C enc. B cable
disconnection
Encoder signal not detected correctly
Note:
It can be disabled by setting C5.n.6.2, where n is the
number of the slot where the accessory is installed.
- Broken or disconnected signal cable.
- Encoder connection error.
- Encoder without power supply.
F1309:
Slot C enc. B cable
disconnection
Encoder signal not detected correctly
Note:
It can be disabled by setting C5.n.6.2, where n is the
number of the slot where the accessory is installed.
- Broken or disconnected signal cable.
- Encoder connection error.
- Encoder without power supply.
A1310:
Slot C enc. Z cable
disconnection
Encoder signal Z not detected correctly
- Broken or disconnected signal cable.
- Encoder connection error.
- Encoder without power supply.
F1311:
Slot C enc. Z cable
disconnection
Encoder signal Z not detected correctly
- Broken or disconnected signal cable.
- Encoder connection error.
- Encoder without power supply.
A1312:
Slot C AI1 cable
disconnection
Analog input signal set to actual mode is out of the
range 4 to 20 mA.
- AI cable broken (the read value was less than 2 mA
for 5 seconds).
Poor contact on the signal connection at the
terminals.
F1313:
Slot C AI1 cable
disconnection
Analog input signal set to actual mode is out of the
range 4 to 20 mA.
- AI cable broken (the read value was less than 2 mA
for 5 seconds).
Poor contact on the signal connection at the
terminals.
A1314:
Slot C AI2 cable
disconnection
Analog input signal set to actual mode is out of the
range 4 to 20 mA.
- AI cable broken (the read value was less than 2 mA
for 5 seconds).
Poor contact on the signal connection at the
terminals.
F1315:
Slot C AI2 cable
disconnection
Analog input signal set to actual mode is out of the
range 4 to 20 mA.
- AI cable broken (the read value was less than 2 mA
for 5 seconds).
Poor contact on the signal connection at the
terminals.
A1316:
Slot C AI3 cable
disconnection
Analog input signal set to actual mode is out of the
range 4 to 20 mA.
- AI cable broken (the read value was less than 2 mA
for 5 seconds).
Poor contact on the signal connection at the
terminals.