English
TROUBLESHOOTING AND MAINTENANCE
Protection/Alarm
Description
Possible causes
F1437:
Slot D sensor 3
overtemperature
Temperature measured by the sensor close to the
threshold level.
- Monitored equipment at a high temperature.
- Fault actuation level configuration error.
A1438:
Slot D temperature
sensor 4 error
Value measured by the temperature sensor out of the
expected range.
- Sensor cable is broken.
- Short-circuited sensor.
- Sensor located in an extremely low temperature
environment.
F1439:
Slot D temperature
sensor 4 error
Value measured by the temperature sensor out of the
expected range.
- Sensor cable is broken.
- Short-circuited sensor.
- Sensor located in an extremely low temperature
environment.
A1440:
Slot D high temperature
in sensor 4
Temperature measured by the sensor close to the
threshold level.
- Monitored equipment at a high temperature.
- Fault actuation level configuration error.
F1441:
Slot D sensor 4
overtemperature
Temperature measured by the sensor close to the
threshold level.
- Monitored equipment at a high temperature.
- Fault actuation level configuration error.
A1442:
Slot D temperature
sensor 5 error
Value measured by the temperature sensor out of the
expected range.
- Sensor cable is broken.
- Short-circuited sensor.
- Sensor located in an extremely low temperature
environment.
F1443:
Slot D temperature
sensor 5 error
Value measured by the temperature sensor out of the
expected range.
- Sensor cable is broken.
- Short-circuited sensor.
- Sensor located in an extremely low temperature
environment.
A1444:
Slot D high temperature
in sensor 5
Temperature measured by the sensor close to the
threshold level.
- Monitored equipment at a high temperature.
- Fault actuation level configuration error.
F1445:
Slot D sensor 5
overtemperature
Temperature measured by the sensor close to the
threshold level.
- Monitored equipment at a high temperature.
- Fault actuation level configuration error.
A1446:
Slot D temperature
sensor 6 error
Value measured by the temperature sensor out of the
expected range.
- Sensor cable is broken.
- Short-circuited sensor.
- Sensor located in an extremely low temperature
environment.
F1447:
Slot D temperature
sensor 6 error
Value measured by the temperature sensor out of the
expected range.
- Sensor cable is broken.
- Short-circuited sensor.
- Sensor located in an extremely low temperature
environment.
A1448:
Slot D high temperature
in sensor 6
Temperature measured by the sensor close to the
threshold level.
- Monitored equipment at a high temperature.
- Fault actuation level configuration error.
F1449:
Slot D sensor 6
overtemperature
Temperature measured by the sensor close to the
threshold level.
- Monitored equipment at a high temperature.
- Fault actuation level configuration error.
F1500:
Slot E incompatible
accessory
Error during accessory firmware update.
Old inverter firmware version.
F1501:
Slot E Initialization Error
It was not possible to initialize a resource required for
the accessory to work.
- Resource already in use by another accessory.
In the case of communication network accessories,
only one accessory of each type of network can be
connected to the inverter at a time.
F1503:
Slot E accessory
connection
Loss of communication with the accessory.
- Above-supported electromagnetic noise.
- Vibration above supported limits causing connector
problems.
- Corrupted accessory firmware.
CFW900 | 79
Summary of Contents for CFW900
Page 2: ......