5
DETAILED PARAMETER DESCRIPTION
Description:
Used in the digital and relay output functions: N = 0 and in the “Stop Logic” (Disable by N = 0; refer to P0211
and P0212).
P0292 - N=N* Band
Adjustable range:
1 to 100 %
Factory setting:
1 %
Acesso:
Menu
→
Configurations
→
Control
Description:
Used in the digital and relay output functions: N = N*.
P0295 - Inverter rated current
Adjustable range:
0 to 28
Factory setting:
10
Acesso:
Menu
→
Configurations
→
Nominal data
→
Inverter
Description:
It defines the inverter rated current according to the available models.
Table 5.46:
Inverter rated current
Function
0
24 A
1
40 A
2
50 A
3
60 A
4
70 A
5
80 A
6
90 A
7
100 A
8
110 A
9
125 A
10
140 A
11
160 A
12
180 A
13
200 A
14
225 A
15
265 A
16
310 A
17
340 A
18
400 A
19
450 A
20
500 A
21
550 A
22
600 A
23
650 A
24
700 A
25
750 A
26
800 A
27
850 A
28
900 A
✓
NOTE!
This parameter can be changed only with the motor stopped.
MVW3000 | 5-65
Summary of Contents for MVW3000 Series
Page 2: ......
Page 58: ...1 QUICK REFERENCE OF PARAMETERS AND FAULTS MVW3000 1 52...
Page 62: ...2 SAFETY INSTRUCTIONS MVW3000 2 4...
Page 192: ...6 SPECIAL FUNCTIONS MVW3000 6 4...
Page 262: ...7 DIAGNOSTICS AND TROUBLESHOOTING MVW3000 7 70...
Page 263: ......