5
DETAILED PARAMETER DESCRIPTION
Table 5.50:
Disabling with alarm A128, A129 and A130
Function
0
Disable via Run/Stop
1
Disable via General Enable
2
Inactive
3
Go to LOCAL
4
Not Used
5
Fatal Failure
P0314 - Time for serial watchdog action
Adjustable range:
0.0 to 999.0 s
Factory setting:
0.0 s
Acesso:
Menu
→
Configurations
→
Communications
Description:
If the inverter does not receive any valid serial telegram after the time programmed in P0314, has elapsed,
A0128 will be indicated on the HMI and the inverter will execute the action programmed in P0313 - Disabling
with A0128/A0129/A0130.
For the inverter to be able to execute that action, it is necessary that the commands be programmed for the
“Serial” option in parameters P0220 to P0228.
Table 5.51:
Time for serial watchdog action
Function
0.0
Disabled
0.1 a 999.0
Enabled
✓
NOTE!
This parameter can be changed only with the motor stopped.
P0315 - Function of the MVC3 SCI1 serial channel
Adjustable range:
0 to 2
Factory setting:
0
Acesso:
Menu
→
Configurations
→
HMI
→
Settings
Description:
It selects the function of the SCI1 serial channel of the MVC3 control board.
The module serial configuration must be set as follows:
Baudrate: 2400 bps
Slave address: 1
Parity: even
Stop bit: 1
Table 5.52:
Function of the MVC3 SCI1 serial channel
Function
0
Service HMI
1
Modbus serial for Tecsystem module
2
Modbus Serial for Pextron module
MVW3000 | 5-69