4
HMI OPERATION
4.3.2 Alphanumerical edition
In the edition of message type parameters, the cursor can be moved by using the
and
keys.
Exit
13:38
Save
In Ref.
LOC
0rpm
P0202
Control type
[000] V/f 60 Hz scalar
[001] V/f 50 Hz scalar
[002] Adjustable V/F Scalar
[003] Sensorless Vector
[004] Vector with Encoder
Figure 4.7:
Alphanumerical edition
4.4
CONFIGURING THE HMI
4.4.1
LCD contrast
The HMI LCD contrast is set by the parameter P0490 (Menu
→
Configurations
→
HMI
→
Settings). Typical contrast
values are between 50 and 100.
✓
NOTE!
After the power on, approximately 60 seconds are necessary for the stabilization of the contrast at the
level adjusted in P0490. In certain climatic conditions (temperature/humidity), contrast stabilization
times longer than 60 may occur.
4.4.2
Configuring the HMI Commands
For the HMI commands to work properly, it is necessary to program the local or remote (LOC/REM) inverter
commands to be of the “Graphic HMI” type.
Example of LOCAL configuration:
P0220 = 11 (Graphic HMI
LOC
REM
key (LOCAL Default)).
P0221 = 13 (Graphic HMI
and
key).
P0223 = 12 (Graphic HMI
key (Forward)).
P0224 = 5 (Graphic HMI
|
and
O
key).
P0225 = 6 (Graphic HMI
JOG
key).
Example of REMOTE configuration::
P0220 = 12 (Graphic HMI
LOC
REM
key (REMOTE Default)).
P0222 = 13 (Graphic HMI
and
key).
P0226 = 12 (Graphic HMI
key (Forward)).
P0227 = 5 (Graphic HMI
|
and
O
key).
P0228 = 6 (Graphic HMI
JOG
key).
The automatic programming of the parameters described above may be done through the parameter P0491 “HMI
commands configuration” (Menu
→
Configurations
→
HMI
→
Settings).
MVW3000 | 4-7