5
DETAILED PARAMETER DESCRIPTION
Description:
When the actual speed exceeds the value of P0134 + P0132 for over 20 ms, the MVW3000 will disable the
PWM pulses and indicate fault F0112 (Motor Over Speed).
The setting of P0132 is a percentage value of P0134.
When setting P0132 = 100 % the function will be disabled.
✓
NOTE!
This parameter is only visible on the HMI when: the control type is vector, P0202 = 3 (Sensorless
Vector) or P0202 = 4 (Vector with Encoder).
P0133 - Minimum speed reference
P0134 - Maximum speed reference
Adjustable range:
0 to 7200 rpm
Factory setting:
P0133 = 90 rpm
P0134 = 1800 rpm
Acesso:
Menu
→
Configurations
→
Control
Description:
It defines the maximum/minimum values of speed reference for the motor when the inverter is enabled. Valid
for any type of reference signal.
For details on the actuation of P0133 see P0233 (Dead Zone).
MVW3000 | 5-16