10) Definition among 4 reactive load compensation structures:
- 1.1.1.1 All stages are equal. First-in, first-out (FIFO) is applied. The first stage enabled
will be the first stage to be disabled.
- 1.2.4.4: Stages are sized in the ratio 1.2.4.4. The first stage will always be the first
stage to be enabled or disabled. The other stages are used sequentially.
- 1.2.2.2: Stages are sized in the ratio 1.2.2.2. The first stage will always be the first
stage to be enabled or disabled. Different from the structure above, the other stages
follow the FIFO scheme (first-in, first-out).
- Entr: Stages are set manually. During operation in this structure, the "Smart Mode" is
enabled automatically. The device seeks the best correction with the least possible
number of stages enabled.
PFW03-M8
Settings
– Basic