1.2.1. Explosion protection
The following instructions must be strictly adhered to:
-
Ensure that there is no potentially explosive atmosphere near the machine (absence of
ignition sources)
-
Use only tools that conform to EN 1127-1 in order to prevent sparks
-
Prior to any maintenance or repair work, shut down the power supply to the unit.
Identification
The "Ex" rating plate of the unit is attached to the fan chamber!
The rating information distinguishes between
inside
(processed atmosphere) and
outside
(atmosphere in room of installation). The air handling unit must only be operated under
conditions as specified on the "Ex" rating plate.
Example: the air handling unit is classified as follows (information on "Ex" rating plate:
Ex II 2G c IIB T4 inside ; Ex II 3G c IIB T3 outside
Codes:
Ex = Explosion protection (class)
I
=Equipment group (underground)
II
= Equipment category (above ground)
1
= Protection category 1 (zone 0)
2
= Protection category 2 (zone 1)
3
= Protection category 3 (zone 2)
G
= Gas
IIA = Substances with low ignition susceptibility
IIB = Substances with medium ignition susceptibility
IIC = Substances with high ignition susceptibility
T1 = Max. surface temperature 450° C
T2 = Max. surface temperature 300° C
T3 = Max. surface temperature 200° C
T4 = Max. surface temperature 135° C
T5 = Max. surface temperature 100° C
T6 = Max. surface temperature 85° C
Gases and vapours are classified in three explosion groups (IIA, IIB and IIC), based on their
ignition susceptibility whereby substances in group IIA are less likely to explode than
substances in group IIC.
Summary of Contents for DIWER EVO DP80 Series
Page 2: ......
Page 39: ...Installation and Operating Manual Page 37 Printed 02 2015...
Page 62: ...Installation and Operating Manual Page 60 Printed 02 2015 Notes...
Page 63: ...Installation and Operating Manual Page 61 Printed 02 2015 Notes...
Page 64: ...Installation and Operating Manual Page 62 Printed 02 2015 Notes...