Installation and Operating Manual
Page
23
Printed: 02/2015
4.2. Structural vibration insulation
To prevent structural vibration, we recommend placing cork pads, Mafund sheets, tico pads or
resistant vibration damping mats under the unit. In certain cases, it is advisable to install
vibration dampers. The absorption properties of these materials must be suitable to achieve
optimised structural vibration insulation, depending on the actual load. For weights, please
refer to the technical data sheet. To prevent the propagation of structural vibration, never
screw the units directly to the foundation. We recommend securing the unit with angle
brackets to prevent shifting.
An uneven foundation might cause malfunction of the unit and jammed doors. WEGER shall
not be liable for damage caused by installation on an uneven surface. Roof-mounted central
units are subject to the German Construction Contract Procedures VOB, part C and DIN 18379
as they form part of the technical building services. They are designed and produced according
to best engineering practice and do not constitute part of the actual building structure.
According to EN 13053 and VDI 3803, the base of the unit must not substitute a proper roof
construction. The air handling unit must not fulfil any structural function in the building, such
as sealing or heat insulation.
4.3. Installation of unit
Air handling units for operating theatres must be installed adjacent to the operating theatres.
The unit must be positioned so that there is sufficient space for operating part to access it for
servicing and repair. For details, see section 4.1. Foundation / base frame
Roof frames and weatherproof units must never be used to replace a proper roof structure!
Roof-mounted units (weatherproof models) are protected by a separate weather roof made in
sheet metal. The weather roof is installed at the factory. The joints must be prepared and
sealed as described in section 5.3.3.
Any defects to the coating caused during installation must be repaired.
Summary of Contents for DIWER EVO DP80 Series
Page 2: ......
Page 39: ...Installation and Operating Manual Page 37 Printed 02 2015...
Page 62: ...Installation and Operating Manual Page 60 Printed 02 2015 Notes...
Page 63: ...Installation and Operating Manual Page 61 Printed 02 2015 Notes...
Page 64: ...Installation and Operating Manual Page 62 Printed 02 2015 Notes...