7.9. Heat recovery unit
7.9.1. Plate exchangers
Plate exchangers do not contain any moving parts and are thus virtually maintenance-free. It is
recommended to clean the exchanger regularly and to check the water level in the condensate
tray.
Should the plate exchanger be equipped with a bypass damper, check and clean the damper
regularly. Should the damper be stiff, apply a little silicon spray to the lateral leaf bearings.
7.9.2. Closed-loop system (run around Coils)
To service the closed-loop system, follow the instructions for heat exchangers.
7.9.3. Rotary heat exchanger (thermal Wheel)
Regularly check the drive unit, following the instructions of the manufacturer. The heat storage
medium is self-cleaning.
If necessary, clean the rotor with compressed air or a steam jet cleaner. If there are grease
deposits, clean the heat exchanger with a conventional grease-dissolving detergent.
Blades in segmented rotors must be retightened every 6 months.
7.9.4. Heat tube
Similar to a plate heat exchanger, the heat tube does not contain any moving parts.
Maintenance is thus limited to regular cleaning of the housing.
In addition, perform the maintenance task for the tray and the demister described in section
6.1. Should the heat tube be equipped with a bypass damper, check and clean the valve
regularly. Should the damper be stiff, apply a little silicon spray to the lateral leaf bearings.
7.10. ATEX units
For maintenance work on the air handling unit, follow the instructions in the operating
manuals of the individual devices / overall unit.
WEGER devices are designed for minimum maintenance and many are maintenance-free. The
specified maintenance intervals are guide intervals only and need to be adjusted, depending
on the actual application and air quality.
Non-compliance with the operating and maintenance instructions shall void the manufacturer
warranty.
In the event of a failure of shut-down of the air intake fans, and if the relative air humidity
exceeds 86%, the air humidifiers must be switched off automatically and independently of the
unit operation control.
Summary of Contents for DIWER EVO DP80 Series
Page 2: ......
Page 39: ...Installation and Operating Manual Page 37 Printed 02 2015...
Page 62: ...Installation and Operating Manual Page 60 Printed 02 2015 Notes...
Page 63: ...Installation and Operating Manual Page 61 Printed 02 2015 Notes...
Page 64: ...Installation and Operating Manual Page 62 Printed 02 2015 Notes...