56
The following table summarizes the requirements of the wiring on the PV side. Wires
connected to X1/X4, X2 and the copper busbar shall be made of stranded copper
(preferably PV1–F “solar” wire).
Please check with Weidmüller before using solid or
aluminum wires.
Transclinic 16i+ and Transclinic 16i+ 1k5 L
Transclinic 16i+ 1k5 H
Negative
copper
busbars
Negative PV
current
inputs
Positive PV
voltage
input
Positive
copper
busbar
Positive PV
current
inputs
Negative PV
voltage
input
Terminal / connector
–
X1, X4
X2
–
X1,X4
X2
Stranded wire cross section
(with ferrule)
M6 cable lug /
10 – 35 mm² 2.5 – 10 mm
2
2.5 – 10 mm
2
M6 cable lug /
10 – 35 mm²
2.5 – 16 mm
2
2.5 – 16 mm
2
Stranded wire cross section
(without ferrule)
M6 cable lug /
10 – 35 mm² 2.5 – 16 mm
2
2.5 – 16 mm
2
M6 cable lug /
10 – 35 mm²
2.5 – 16 mm
2
2.5 – 16 mm
2
Stranded wire cross section
for 15 A or 25 A / input
4 × 35 mm
2
PV1–F
6 or 10 mm
2
PV1–F
–
4 × 35 mm
2
PV1–F
6 or 10 mm
2
PV1-F (*)
-
Stranded wire stripping length
–
12 mm ±1 mm 12 mm ±1 mm
-
18 mm ±1 mm 18 mm ±1 mm
Tightening torque
4.0 – 4.5 Nm 1.2 – 1.5 Nm 1.2 – 1.5 Nm
4.0 – 4.5 Nm
No needed
No needed
Required tool
torque
wrench with
10 mm
ISO hex head
torque
wrench with
1 × 5.5 mm
flat-blade
torque
wrench with
1 × 5.5 mm
flat-blade
torque wrench
with 10mm ISO
hex head
-
-
External insulation required
double or
reinforced
double or
reinforced
double or
reinforced
double or
reinforced
double or
reinforced
double or
reinforced
We recommend to use PV cable with higher rated voltage than string voltage of the
application and with a maximum temperature of 120 °C or higher.
For the Transclinic xi+ products with screw connection terminals, we recommend to use
the following devices to tighten the screws.
DMS MANUELL 0.5 – 1.7 Nm 1 9918370000
DMS MANUELL 2.0 – 8.0 Nm 1 9918380000
Summary of Contents for 2008130000
Page 2: ......
Page 14: ...14 ...
Page 19: ...19 Abisolieren Abisolieren Option 1 Option 2 empfohlen Crimpen Drücken Einführen Einführen ...
Page 37: ...37 ...
Page 42: ......
Page 54: ...54 ...
Page 59: ...59 Strip Strip Option 1 Option 2 recommended Crimp Press Insert Insert ...
Page 77: ...77 ...
Page 82: ...82 ...
Page 94: ...94 ...
Page 99: ...99 被覆剥き 被覆剥き オプション 1 オプション 2 推奨 圧着 押し込み 挿入 挿入 ...
Page 117: ...117 ...
Page 126: ......
Page 127: ......