The WI-GTWY-9-xxx also monitors its battery voltage and supply voltage. These are stored in
registers 4310 and 4311 respectively, as 16 bit values, scaled so that a value of 16384 decimal
(hex 4000) corresponds to 8 V, and a value of 49152 (hex C000) corresponds to 40V.
A low battery alarm is available at register 4308. This becomes active when the battery voltage
falls below 11.3V, and clears when the battery voltage rises above 11.8V. Supply voltage is also
monitored, and an alarm is available at register 4309. This becomes active if the supply voltage
falls below 8.0V, and clears when the supply voltage rises above 9.0V.
I/O Register Description
I/O Register Description
4300
Input value DIO 1
4320
Output value DIO 1
4301
Input value DIO 2
4321
Output value DIO 2
4302
Input value DIO 3
4322
Output value DIO 3
4303
Input value DIO 4
4323
Output value DIO 4
4304
Input value DIO 5
4324
Output value DIO 5
4305
Input value DIO 6
4325
Output value DIO 6
4306
Input value DIO 7
4326
Output value DIO 7
4307
Input value DIO 8
4327
Output value DIO 8
4308
Low battery voltage status
4309
Supply voltage fail status
4310
Battery voltage value
4311
Supply voltage value
4370 - 4379
Inverse values of
4300 - 4309