28
Manual maxGUARD
2526740000/02/03.2018
4 Configuration
| Example configurations
Example: One segment with connection to a control unit
Example: maxGUARD station with connection to a control unit
This example shows a control voltage distributor for six se-
lectively fused load circuits with connection to a control unit.
The following maxGUARD products are used:
–
1x AMG FIM-C
–
1x AMG ELM-6
–
1x AMG ELM-4F
–
1x AMG ELM-Q2222
–
1x AMG PD
–
2x AMG OD
–
1x AMG MD
–
1x AMG XMD
–
2x AMG EP
–
2x WEW 35/2
–
1x ZQV 4N/50 RD, 1x ZQV 4N/3 RD, 1x ZQV 4N/2 RD
–
1x ZQV 4N/50
–
1x ZQV 4N/50 BL, 2x ZQV 4N/3 BL
The active feed-in module feeds in the supply voltage and
connects the station to the control unit.
The potentials are distributed to the individual modules via
cut cross-connectors. As the total current flowing through
the station is less than 20 A, the main strands are each
equipped with only one cross-connector. The internal signal
line is established via a cut cross-connector.
The outputs of the load monitors are replicated using poten-
tial distribution terminals. The potential distribution terminals
are connected to the outputs of the load monitors via uncut
cross-connectors.
The station must be equipped with end plates at both ends.
Only then will the exposed cut edges of the cut cross-con-
nector be insulated and the exposed side of the last potential
distribution terminal covered.